Calculo de Sistemas de Bombeos
-
Upload
ricardo-enriquez -
Category
Documents
-
view
20 -
download
3
description
Transcript of Calculo de Sistemas de Bombeos
ANALISIS A CAUDAL MAXIMO HORARIO - SIN COMPRESOR ANALISIS A CAUDAL MAXIMO HORARIO - CON COMPRESOR3.00
CAUDAL MAXIMO HORARIO 19.61 l/s CAUDAL MAXIMO HORARIO 19.61 l/s
CAUDAL DE BOMBEO 23.53 l/s
4.50
0.75 Ve =3.53
CAUDAL DE BOMBEO 23.53 l/s
NUMERO DE CICLOS U = 4.00 HORA CAUDAL DE AGUA + AIRE 16.16 l/s
TIEMPO DE BOMBEO Tc = 900.00 s VOLUMEN DE AIRE 3.53 m2
VOLUMEN UTIL Vu = 4.41 m3
3.00 Ve =21.21
VOLUMEN DE UTIL DE AGUA 21.21 m3
PRESION MINIMA 30.00 m TIEMPO DE BOMBEO 9.88 min
PRESION MAXIMA 45.00 m TIEMPO DE VACIADO 18.03 MIM
PORCENTAJE DE VOLUMEN %Vu = 30% % DE ENERGIA POR CICLO 0.35VULUMEN TOTAL Vt = 14.71 m3 TIEMPO DE CICLO Tc = 27.91 MIMDIAMETRO D = 3.00 m CICLOS HORA A CMH Nc = 2.15
ALTURA DE TANQUE H = 4.50 m
0.75 Ve =3.53
TIEMPO USO BOMBA+ COMPRES Tu = 21.25 MIN
AREA DE TANQUE A = 7.07 m2 POTENCIA BOMBA + COMPRES 30.00 HP
TIEMPO DE BOMBEO 3.13 min POTENCIA BOMBA + COMPRES 22.20 KwTIEMPO DE VACIADO 3.75 min FACTOR DE ARRANQUE F = 0.28
% DE ENERGIA POR CICLO 0.45 ENERGIA HORA E = 8.08 Kw/HORATIEMPO DE CICLO Tc = 6.88 minCICLOS HORA A CMH Nc = 8.73TIEMPO USO BOMBA Tu = 27.27 min
POTENCIA SISTEMA DE BOMBEO 20 HP
POTENCIA SISTEMA DE BOMBEO 15 KwFACTOR DE ARRANQUE F = 0.55ENERGIA HORA E = 9.00 Kw/HORA
ANALISIS A CAUDAL MEDIO DIARIO - SIN COMPRESOR ANALISIS A CAUDAL MEDIO DIARIO - CON COMPRESOR3.00
CAUDAL MEDIO DIARIO 13.07 l/s CAUDAL MAXIMO HORARIO 19.61 l/s
CAUDAL DE BOMBEO 23.53 l/s4.
50
0.75 Ve =3.53
CAUDAL DE BOMBEO 23.53 l/s
NUMERO DE CICLOS U = 4.00 HORA CAUDAL DE AGUA + AIRE 16.16 l/s
TIEMPO DE BOMBEO Tc = 900.00 s VOLUMEN DE AIRE 3.53 m2
VOLUMEN UTIL Vu = 4.41 m3
3.00 Ve =21.21
VOLUMEN DE UTIL DE AGUA 21.21 m3
PRESION MINIMA 30.00 m TIEMPO DE BOMBEO 12.09 min
PRESION MAXIMA 45.00 m TIEMPO DE VACIADO 27.04 min
PORCENTAJE DE VOLUMEN %Vu = 30% % DE ENERGIA POR CICLO 0.31VULUMEN TOTAL Vt = 14.71 m3 TIEMPO DE CICLO Tc = 39.13 minDIAMETRO D = 3.00 m CICLOS HORA A CMH Nc = 1.53
ALTURA DE TANQUE H = 4.50 m
0.75 Ve =3.53
TIEMPO USO BOMBA+ COMPRES Tu = 18.54 min
AREA DE TANQUE A = 7.07 m2 POTENCIA BOMBA + COMPRES 30.00 HP
TIEMPO DE BOMBEO 3.13 MIM POTENCIA BOMBA + COMPRES 22.20 KwTIEMPO DE VACIADO 5.63 MIM FACTOR DE ARRANQUE F = 0.32
% DE ENERGIA POR CICLO 0.36 ENERGIA HORA E = 7.01 Kw/HORATIEMPO DE CICLO Tc = 8.75 MIMCICLOS HORA A CMH Nc = 6.86TIEMPO USO BOMBA Tu = 21.43 MIN
POTENCIA SISTEMA DE BOMBEO 20 HP
POTENCIA SISTEMA DE BOMBEO 14.8 KwFACTOR DE ARRANQUE F = 0.70ENERGIA HORA E = 7.00 Kw/HORA
QB = QB =
QSB = QSB =
QAireyAgua =
VE =
Vc =
PMIN = TLL =
PMAX = TV =
TLL/(TLL+TV) =
PSB =
TLL = PSB =TV=
TLL/(TLL+TV)=
PSB =
PSB =
QB = QB =
QSB = QSB =
QAireyAgua =
VE =
Vc =
PMIN = TLL =
PMAX = TV =
TLL/(TLL+TV) =
PSB =
TLL = PSB =TV=
TLL/(TLL+TV)=
PSB =
PSB =