EJEMPLO DE DISEÑO DE LARGUERO Y ALINEADOR
-
Upload
lucius-roma -
Category
Documents
-
view
53 -
download
8
Transcript of EJEMPLO DE DISEÑO DE LARGUERO Y ALINEADOR
OBRA:
UBICACIÓN:
LOCALIDAD:
VALUACIÓN DE CARGAS PARA LARGUEROS
ÁREA TRIBUTARIA DE LARGUERO= 8.00 x 1.23 = 9.84 M2
PESO DE LÁMINA PINTRO CAL. 26 8.00 KG/M2
PESO DE LARGUERO 8 MT 10 ( 8.9 KG/ML ) 9.70 x 8.00 = 77.60
77.60 / 9.84 = 7.89 KG/M2
PRESIÓN DE VIENTO 45.00 KG/M2
CARGA VIVA= 20.00 KG/M2
TOTAL= 80.89 KG/M2
CARGA TOTAL QUE SOPORTA EL LARGUERO= 795.92 KGS APROX. 796.00 KG
CARGA POR ML= 99.50 KG/M
ÁREA TRIB. DE CARGA POR LARGUERO= 8.00 x 1.23 = 9.84 M2
ÁNGULO DE INCLINACIÓN DE LA ARMADURA= 14.15 GRADOS = 0.25 RAD
CARGA EN EJE " X "= W x COS θ = 96.48 KG/ML
CARGA EN EJE " Y "= W x SEN θ = 24.32 KG/ML
SI SE UTILIZAN 1.00 ALINEADOR
MOMENTO EN " X "= w l ^2 / 8 = 771.85 KG - M = 77,184.86 KG - CM
MOMENTO EN " Y "= w l ̂2 / 32 = 48.65 KG - M = 4,864.78 KG - CM
PARA UN PERFIL MONTEN 8 MT 12 Sx= 71.92 CM3 Sy= 13.97 CM3
Fbx= 0.66 x 2,530.00 = 1,669.80 KG/CM2
Fby= 0.75 x 2,530.00 = 1,897.50 KG/CM2
77,184.86 4,864.78
71.92 13.97
fbx fby 1,073.20 348.23
Fbx Fby 1,669.80 1,897.50
SE PROPONEN LARGUEROS CON PERFIL MONTEN 8 MT 10 @ EN CADA NODO DE LA CUERDA SUPERIOR
OK
348.23 KG/CM2
+ = + = 0.83 < 1.00
fbx= = 1,073.20 KG/CM2 fby= =
OBRA:
UBICACIÓN:
LOCALIDAD:
DISEÑO DE ALINEADORES
ÁREA TRIBUTARIA PARA UN ALINEADOR 4.00 x 1.23 = 4.92 M2
ÁREA TRIBUTARIA PARA EL ALINEADOR MÁS CRÍTICO= 4.00 x 12.50 = 50.00 M2
PESO DE LÁMINA PINTRO CAL. 26 8.00 KG/M2
PESO DE LARGUERO 8 MT 10 ( 8.9 KG/ML ) 9.70 x 4.00 = 38.80
38.80 / 4.92 = 7.89 KG/M2
PRESIÓN DE VIENTO 45.00 KG/M2
CARGA VIVA= 20.00 KG/M2
TOTAL= 80.89 KG/M2
REACCIÓN MÁXIMA= 50.00 x 80.89 = 4,044.31 KG
ÁNGULO DE INCLINACIÓN DE LA ARMADURA= 14.15 GRADOS = 0.25 RAD
CARGA EN EJE " X "= W x COS θ = 3,921.60 KG
CARGA EN EJE " Y "= W x SEN θ = 988.68 KG
TENSIÓN MÁXIMA= 988.68 KG
PROPONIENDO UN REDONDO SÓLIDO LISO DE 1/2 PLG A= 1.27 CM2
fy= 2,530.00 KG/CM2 fpermisible= 0.60 x 2,530.00 = 1,518.00 KG/CM2
988.68
1,518.00
SE ACEPTA EL PERFIL
SE PROPONE UN DÁMETRO DE 1/2" @ CENTRO DE LARGUERO COMO ALINEADOR
CM2 < 1.27A=TENSIÓN MÁXIMA
ESFUERZO PERMISIBLE= = 0.65