PREDIMENSIONAMIENTO DE ELEMENTOS ESTRUCTURALESLOSA ALIGERADA

L (m) FACTOR

4.68 25.00 0.19

VIGASVIGA PRINCIPAL

L (m) FACTOR

7.00 10.00 0.70

B (m)0.30 SE USA EL ANCHO MINIMO PARA VIGA PRINCIPAL

LA VIGA PRINCIPAL SERA DE : 0.30m. X 0.70m.

VIGASVIGA SECUNDARIA

L (m) FACTOR

4.68 10.00 0.47

NOTA: POR DECISION PROPIA PARA EN ANALISIS SE USARA LA MISMA ALTURA DE LA VIGA PRINCIPAL

B (m)0.30 SE USA EL MISMO ANCHO QUE LA VIGA PRINCIPAL

LA VIGA SECUNDARIA SERA DE : 0.30m. X 0.70m.

COLUMNAS

PS n f'c (Kg/cm2)

92181.60 0.45 280

DETERMINACION DE LA CARGA DE SERVICIO PS

Kg/m3 Kg/m2 LONGITUD 1LOSA ALIGERADA 300.00 3.50VIGA SECUNDARIA 2400.00VIGA PRINCIPAL 2400.00ACAB. + TABIQU. 250.00 3.50COLUMNA 2400.00

ALTURA DE LOSA ALIGERADA

ALTURA DE VIGA PRINCIPAL

ALTURA DE VIGA SECUNDARIA

Page 2: Metrado de Cargas v01

SOBRECARGA 250.00 3.50

VERIFICACION DEL AREA DE COLUMNA1000cm21000cm2

ALTERNATIVA PARA ANCHO DE COLUMNAH de viga

0.70VERIFICACION DEL AREA DE COLUMNA

1000cm21000cm2

LA COLUMNA SERA DE : 0.56m. X 0.30m.

COLOCACION DE CARGASLOSA ALIGERADA

CARGA MUERTAPESO DEL LADRILLO 80.00 Kg/m2TABIQ. + ACAB. 250.00 Kg/m2

330.00 Kg/m2

0.40 m.

CARGA DISTRIBUIDA 132.00 Kg/m

CARGA VIVAS/C 250.00 Kg/m2

250.00 Kg/m2

0.40 m.

CARGA DISTRIBUIDA 100.00 Kg/m

CALCULO DEL PESO 2°,3°y 4° piso

Kg/m3 Kg/m2 LONGITUD 1

LOSA ALIGERADA 300.00 7.00VIGA PRINCIPAL 2400.00VIGA SECUNDARIA 2400.00ACAB. + TABIQU. 250.00 7.00COLUMNA 2400.00SOBRECARGA 250.00 7.00

CALCULO DEL PESO 5°PISO

ANCHO SUPERIOR DE LOSA ALIGERADA

ANCHO SUPERIOR DE LOSA ALIGERADA

Page 3: Metrado de Cargas v01

Kg/m3 Kg/m2 LONGITUD 1

LOSA ALIGERADA 300.00 7.00VIGA PRINCIPAL 2400.00VIGA SECUNDARIA 2400.00ACABADOS 100.00 7.00COLUMNA 2400.00SOBRECARGA 100.00 7.00

CALCULO DEL PESO 1°PISO

Kg/m3 Kg/m2 LONGITUD 1

LOSA ALIGERADA 300.00 7.00VIGA PRINCIPAL 2400.00VIGA SECUNDARIA 2400.00ACAB. + TABIQU. 250.00 7.00COLUMNA 2400.00SOBRECARGA 250.00 7.00

DX 7.00 mDY 21.00 m

CALCULO DE LA CORTANTE BASAL

Z 0.4U 1Cx 2.5Cy 2.5S 1.4R 8

Vx 0.175

Vy 0.175

V=𝑍𝑈𝐶𝑆/𝑅 𝑋 𝑃

Vx=𝑍𝑈𝐶𝑆/𝑅 Vy=𝑍𝑈𝐶𝑆/𝑅

Page 4: Metrado de Cargas v01

FACTOR DE AMPLIFICACION SISMICA ( C )

Tx= 0.43428571429 mH 15.20

Ctx= 35Tp= 0.9

Cx 5.18092105263Cx 2.5

VX 0.175*P 122518.767 KGVY 0.175*P 122518.767 KG

NIVELES ALT ACUM. PESO ALT*PESO5 15.200 112068.600 1703442.7204 12.200 146888.700 1792042.1403 9.200 146888.700 1351376.0402 6.200 146888.700 910709.9401 3.200 147372.540 471592.128

700107.240 6229162.968

x -8.5y -1.5

Cx=2.5 𝑋 (𝑇𝑝/𝑇𝑥 ) ≤ 2.5

Page 5: Metrado de Cargas v01

0.20 m

m

SE USA EL ANCHO MINIMO PARA VIGA PRINCIPAL

0.70 m

NOTA: POR DECISION PROPIA PARA EN ANALISIS SE USARA LA MISMA ALTURA DE LA VIGA PRINCIPAL

SE USA EL MISMO ANCHO QUE LA VIGA PRINCIPAL

^

AREA DE COLUMNA

731.6 cm2

LONGITUD 2 ALTURA SECCION 1 SECCION 2 N° DE PISOS4.68 5.004.68 0.70 0.30 5.003.50 0.70 0.30 5.004.68 5.00

3.00 0.30 0.56 5.00

ALTURA DE LOSA ALIGERADA(red.)

ALTURA DE VIGA SECUNDARIA A USAR

Page 6: Metrado de Cargas v01

4.68 5.00

PS

≤ A. columna ≥ 2000cm2≤ 731.6 ≥ 2000cm2 NO PASA

% ANCHO DE COLUMNA80% 0.56 m

≤ A. columna ≥ 2000cm2≤ 1680.00 ≥ 2000cm2 OK

LA COLUMNA SERA DE : 0.56m. X 0.30m.

LONGITUD 2 ALTURA SECCION 1 SECCION 2 CANTIDAD

21.00 1.007.00 0.70 0.30 6.00

21.00 0.70 0.30 2.0021.00 1.00

3.00 0.56 0.30 12.0021.00

Page 7: Metrado de Cargas v01

LONGITUD 2 ALTURA SECCION 1 SECCION 2 CANTIDAD

21.00 1.007.00 0.70 0.30 6.00

21.00 0.70 0.30 2.0021.00 1.00

1.50 0.56 0.30 12.0021.00

LONGITUD 2 ALTURA SECCION 1 SECCION 2 CANTIDAD

21.00 1.007.00 0.70 0.30 6.00

21.00 0.70 0.30 2.0021.00 1.00

3.10 0.56 0.30 12.0021.00

Page 8: Metrado de Cargas v01

Tx= 0.4342857142857 mH 15.20

Ctx= 35Tp= 0.9

Cy 5.1809210526316Cy 2.5

F SISMICA X VX MTZ X F SISMICA Y VY33504.293 33504.293 35179.508 33504.293 33504.29335246.918 68751.211 37009.263 35246.918 68751.21126579.643 95330.853 27908.625 26579.643 95330.85317912.368 113243.221 18807.986 17912.368 113243.221

9275.546 122518.767 9739.323 9275.546 122518.767122518.767 122518.767

Cy=2.5 𝑋 (𝑇𝑝/𝑇𝑥 ) ≤ 2.5

Page 9: Metrado de Cargas v01

PESO PARCIAL24570.0011793.60

8820.0020475.00

6048.00

Page 10: Metrado de Cargas v01

20475.00

92181.60 Kg.

PESO PARCIAL

44100.0021168.0021168.0036750.0014515.20

25% 9187.50

146888.70 Kg. Para 2°,3°y 4°piso

factor RNE art.16.3

Page 11: Metrado de Cargas v01

PESO PARCIAL

44100.0021168.0021168.0014700.00

7257.6025% 3675.00

112068.60 Kg.

PESO PARCIAL

44100.0021168.0021168.0036750.0014999.04

25% 9187.50

147372.54 Kg.

factor RNE art.16.3

factor RNE art.16.3

Page 12: Metrado de Cargas v01

MTZ Y11726.50312336.421

9302.8756269.3293246.441

Page 13: Metrado de Cargas v01

CARGAS DE FUERZA AXIAL Kgf

EJE A-1EJE A-2EJE A-3EJE A-4EJE A-5EJE A-6

Page 14: Metrado de Cargas v01

DISTORSIONES ELASTICAS

N° DE PISOSX SY

X Y X Y1 0 0 0.00019 0.0025752 0.002019 0.000058 0.000193 0.0026123 0.001045 0.000049 0.000156 0.0022364 0.001467 0.000034 0.000116 0.0017075 0.000955 0.000017 0.000065 0.001003

LO SOLICITADO POR LA NORMA E-030 0.007

DISTORSIONES INELASTICAS

N° DE PISOSX SX

X Y X Y1 0.00000000 0.00000000 OK OK2 0.01211400 0.00034800 NO PASA OK3 0.00627000 0.00029400 NO PASA OK4 0.00880200 0.00020400 NO PASA OK5 0.00573000 0.00010200 OK OK

N° DE PISOSY SY

X Y X Y1 0.00114000 0.01545000 OK NO PASA2 0.00115800 0.01567200 OK NO PASA3 0.00093600 0.01341600 OK NO PASA4 0.00069600 0.01024200 OK NO PASA5 0.00039000 0.00601800 OK NO PASA