Tcv-3035 Horno Regeneracion
-
Upload
camilo-ernesto-nardez-martinez -
Category
Documents
-
view
220 -
download
0
Transcript of Tcv-3035 Horno Regeneracion
-
7/27/2019 Tcv-3035 Horno Regeneracion
1/9
-
7/27/2019 Tcv-3035 Horno Regeneracion
2/9
2
M/CDKarlDungsInc.FRGR
atioRegulator/ZeroGovernorEdition2012.05P/N261401
Specication
Max. Operating Pressure (MOP)7 PSI (500 mbar)5 PSI (350 mbar) applies to the CSACertication.
Ambient / Fluid TemperatureFRG 7../6 series: +5 F to +160 F for up to 7 PSI for
regulating behavior(+/- 10 % of setpoint)
CSA Certied for -40F to +160 Ffor up to 5 PSI: Diaphragms are
suitable for the low temperature,but there may be out of rangeregulating behavior.
GasesDry, natural gas, propane, butane;other noncorrosive gases. Suitablefor up to 0.1 % by volume, dry H
2S.
A dry gas has a dew point lowerthan +15 F and its relative humidityis less than 60 %.Materials in contact with Gas
Housing: AluminumSeals & Diaphragm: NBR-basedrubber
F
0
-40
+160
FRG/6 Spring-loaded ratio regulator / zero governor with adjustable setpoint spring and dened counterspring. Internal
sensing of output pressure; air impulse line connection is standard.
Optimal Inlet Pressure RangeRatio Regulator: 3 to 80 in. W.C.(7 to 200 mbar)Zero Governor: 3 to 20 in. W.C.(7 to 50 mbar)Output Pressure RangeRatio Regulator: -4 to 60 in. W.C.(-10 to 150 mbar)
Zero Governor: -2 to 1 in. W.C.(-5 to 3 mbar)
Gas
Body Size Order No. Size
FRG 705/6 259-157 1/2 NPT
FRG 707/6 259-158 3/4 NPT
FRG 710/6 259-159 1 NPT
FRG 712/6 259-228 1 1/4 NPT
FRG 715/6 259-160 1 1/2 NPT
FRG 720/6 259-161 2 NPT
FRG 725/6 259-162 2 1/2 NPT
FRG 730/6 259-163 3 NPT
[PSI]
Vent Limiting Device and Vent LineConnectionThe FRG/6 has an internal, factoryinstalled vent limiter, which limitsthe escape of gas to less than 0.5CFH @ 5 PSI in case atmosphericdiaphragm ruptures. Vent limitingdevice also complies with EN 88 &ISO 2355-1. Venting required unlessotherwise accepted by the authority
having jurisdiction.
-
7/27/2019 Tcv-3035 Horno Regeneracion
3/9
3 9
M/CDKarlDungsInc.FRGR
atioRegulator/ZeroGovernorEdition2012.05P/N261401
Recommended Mounting ProcedureRegulator dome from vertically upright to lying horizontally
Mounting
If the ow is not in the same direction of the
arrows, the regulator will not operate properly.
Recommended Preparation The main gas supply must be shut o before starting the
installation. Read these installation instructions carefully.
Carefully examine the FRG/6 for shipping damage. Remove the two red plastic covers from the FRG/6 body.
Remove all dirt and debris before installing the FRG/6. Fail-ure to remove dirt/debris could result in damage or improperperformance.
Recommended Procedure to Mount the FRG/6
Install the FRG/6 with the gas ow matching the directionindicated by the arrows on the casting.
Mount the FRG/6 with the regulator vertical or horizontal. Use new, properly reamed and threaded pipe free of chips. Apply good quality pipe sealant, putting a moderate amount
on the male threads only. If using LP gas, use pipe sealantrated for use with LP gas.
Do not thread pipe too far. FRG/6 distortion and/or malfunc-tion may result from excess pipe in the valve body.
Apply counter pressure with a parallel jaw wrench only tothe ats of the FRG/6 when installing pipe.
Do not overtighten the pipe. Follow the maximum torque
values listed.
After installation is complete, perform a leak test.
As a proportionator, this is an air impulse line connection. Asa zero govenor, this is a breathing plug or a vent connection.
NOTE: All FRGs have a factory installed vent limiting device
under the regulator housing. Connection is G 1/4 for FRG705/6 to FRG 710/6 and G 1/2 for FRG 712/6 to FRG 730/6.G thread to NPT thread adapters are available. G 1/4 to
1/4NPT adapter (part number 231-944) and G 1/2 to 1/2NPT adapter (part number 231-945).
Pressure tap connection in inlet section, both sides 1/4 NPT. Pressure tap connection in outlet section, both sides 1/4 NPT.
1
2
3
NPTpipe 3 1 1 1
2 2 3
Tmax
[Ib-in]443 752 1106 1770 1991 2213 2876 35If the ow is not in the same direction as the
arrows, the FRG/6 will not operate properly.
Pressure Taps/Air Impulse Line/Vent Connection
Test PortWhen low re bypass is us
only test ports on one scan be used.
2 3
Low re bypass option for 705/6 - 720/6P/N 225-256
-
7/27/2019 Tcv-3035 Horno Regeneracion
4/9
4
M/CDKarlDungsInc.FRGR
atioRegulator/ZeroGovernorEdition2012.05P/N261401
Application - Zero governor
For use with gas engines or premix burners, the FRG controlsow by reducing upstream gas pressure to zero or adjustable
to slightly above or below atmospheric pressure.
The outlet pressure is adjustable with the setpoint spring.
For Vmax
see ow diagram on page 6.
Outlet pressure
p2 [W.C.]
Vmax. at high fireV [CFH]
The above illustration shows adjustability (fuel biasing) of the FRG/6 when used as a zero governor. Refer to page 6 for siz-
ing FRG/6 at maximum ow rate.
Zero governor outlet pressure
Gas Equipment
Gas
FRG/6Mixer
Air Filter
Adjusting the FRG/6
1. For zero governor applications, the FRG should be ad-justed at low re only.
2. If the FRG is not owing enough gas at the maximum airow rate, the gas ow can be increased by any of the
following:a.) Increase the negative signal to the FRG.b.) Install a larger FRG.
Zero Governor Application
Do not mount the zero governor upside down.
-
7/27/2019 Tcv-3035 Horno Regeneracion
5/9
5 9
M/CDKarlDungsInc.FRGR
atioRegulator/ZeroGovernorEdition2012.05P/N261401
Application - Ratio Regulator
The FRG holds a constant gas/air ratioduring turndown by varying gas ow to
the burner in proportion to the combus-tion air ow. Adjustable for excess air
or gas.
Setup Procedure
When setting up the FRG/6 and burnerfor proper ratio at all ring rates, follow
the burner manufacturers instructions.The following procedure contains recom-
mended guidelines only, and they do notsupercede the burner manufacturersprocedures for setting up and adjusting
the FRG/6 to the burner.
Low Fire AdjustmentThe adjustable top loading spring on the
FRG/6 is a low re adjustment (see outletpressure adjustment on page 2). If the
tension on this spring is at a minumumand there is still too much gas ow at lowre, achieving a lower ow rate is possible
by reducing the air impluse line pressureto 2WC or less. If the air impluse line
pressure cannot be reduced, a lowerow rate can be acheived by installing
a smaller FRG/6.In order to achieve a low re ow rate inthe range of 20-100 CFH, a eld mount-
able low re bypass restrictor (225-256)is recommended. See Flow curve for
Low re bypass on page 5 for more
details. When using the low re bypassrestrictor, it is recommended that the top
loading spring be adjusted so that theFRG/6 regulating disc opens just as theimpulse line increases during the ramp-
up cycle. If the loading spring tension istoo small, there will be a delayed increase
of fuel ow as the air ow increase untilthe loading line pressure is greater than
the counterspring force, and the result
can be a lean burner over a small rangeof inputs near low re.
CAUTION: Multiple burners and lowre adjustment. It is not recommended
to use a control scheme or gas pipingscheme that does not equally distribute
the gas pressure to each burner at lowre. Examples of such shemes couldinclude using one FRG/6 to control the
gas ow to more than one burner, orusing one air control valve to feed two
FRGs and a second air control valve tofeed three FRGs. Such a control scheme
will likely not allow for optimal low readjustment at each burner.CAUTION: Purge and low re start.
A burner ( or set of burners) that lightimmediately after a purge that is longer
the 60 seconds can cause a 5-20 sec-ond (depending on the purge pressure)
slightly fuel rich condition at the low restart. If such a case occurs, it is recom-
mended that the loading line pressureduring the purge be vented, or thatligho be delayed just lone enough to
eliminate the slightly fuel rich condition
at the low re start.
High Fire Adjustment
Additional adjustments might be neeat high re, depending on the type
burner, piping arrangement, ow,impluse line pressure, and the mode
FRG/6 installed on the burner. NOThe burner might have an integrated limiting valve or an air balancing va
(see illustration below). If these areprovided on the burner, installing th
might be needed in order to achievecorrect ratio at high re.
In cases where the high re rate is rich, partially close the gas limiting valocated downstream of the FRG/6
order to achieve proper ratio. This justment reduces the gas pressure in
burner without aecting the air pressRe-adjust the low re ratio if needed
In cases where the high ring rate is lean, rst verify that the inlet gas press
to the FRG/6 is and remains at least 2Whigher than the air impluse line pressat high re. If there is suitable inlet
pressure to the FRG/6, then more to the burner can be accomplished
either installing a larger FRG/6 orpartially closing the air balancing va
located downstream of the control vato achieve proper ratio; this adjustmreduces the air pressure in the bur
and increases the impulse line presson the FRG/6. Re-adjust the low
ratio if needed.
Adjusting the FRG/6See out pressure adjustment on pag
Buttery Control Valve
Bias(Low Fire adjustment ONLY)
FRG/6Gas Limiting Valve(High Fire Adjustment)
Air Balancing Valve(High Fire Adjustment)
Burner
Two pipediameters MIN. Five pipe diameters MIN.
Air impusleloading line
Ratio Regulator Application
The size of the air impulse
line should match the FRG/6air impulse line connection. Itshould be as short as possible
with as few bends as possible
The low re air impulse linepressure should be between
0.2 and 1.0 In. W.C.
Do not mount the FRG
upsidedown.
-
7/27/2019 Tcv-3035 Horno Regeneracion
6/9
6
M/CDKarlDungsInc.FRGR
atioRegulator/ZeroGovernorEdition2012.05P/N261401
40
30
20
10
0.95 (gas) : 1 (air)
225-256
Mounting the Low Fire Bypass
1. Remove the pressure tap plate with a
Torx driver size T20.2. Line up the low re bypass making
sure that the O-ring is seated cor-rectly. Reinstall with the screws fromthe pressure tap mounting plate.
3. Perform a leak test after torquing thelow re bypass.
Adjusting the Low Fire Bypass
1. Remove the black cover
2. With a slotted screwdriver turn theadjustment screw clockwise for LESS
gas and counter clockwise for MOREgas ow.
3. Secure cap with a wire seal.
Low re bypass Flow adjustmentMounting of low re bypass
The above illustration shows that the air impulse line can be adjusted to achieve excess air, excess gas, or on ratio at low
re. However, the air impulse line slightly exceeds the gas outlet pressure at high re rate.
Flow Curve for Low re bypass
Ratio Regulator Biasing Curve
Low Fire Bypass
Ratio Regulator Biasing Curve
Low re bypass max. Torque
1.85 Lb-in.
The low re bypass is factory
set for maximum ow.
, Please note: only FRG 705/6 - 720/6
-
7/27/2019 Tcv-3035 Horno Regeneracion
7/9
7 9
M/CDKarlDungsInc.FRGR
atioRegulator/ZeroGovernorEdition2012.05P/N261401
Cover Top View
Adjusting the FRG/61. Remove the black cover.
2. To increase outlet pressure turn the adjustment spindleclockwise, to decrease the outlet pressure turn the adjust-
ment spindle counterclockwise.3. Always use an accurate pressure guage connected down
stream from the requlator to measure the actual outletpressure.
4. Reinstall the black cover.5. After adjusting the set point for normal operation check tosee that the gas pressure regulator operates as intended.
6. Use holes in the black cover and the side of the regulatorto secure a lead seal to prevent unauthorized adjustment.
Outlet Pressure Adjustment
13
An internal adjustment limits (but does not pre-vent) the risk of a gas rich ame.
-
7/27/2019 Tcv-3035 Horno Regeneracion
8/9
8
M/CDKarlDungsInc.FRGR
atioRegulator/ZeroGovernorEdition2012.05P/N261401
Pressure Drop for other Gases
To determine the pressure drop when using a gas other than
natural gas, use the ow formula below and f value locatedin the table below to determine the corrected ow rate in
CFH through the valve for the other gas used. For example,
when using propane, divide the volume (CFH) of propane
required for the application by the calculated value f (f = 0.66for propane). Use this corrected ow rate and the ow curve
on the next page to determine pressure drop for propane.
Density of Natural gas
Density of gas usedf =
Type of gas Density[kg/m3]
s.g. f
Natural gas 0.81 0.65 1.00
Butane 2.39 1.95 0.58
Propane 1.86 1.50 0.66
Air 1.24 1.00 0.80
Determining equivalent ow through valves using another gas
Vgas used
= VNatural gas
x f
FRG/6 Flow Curve
A minimum of 3 in. W.C. p is required when sizing at maximum ow capacity for optimal control on high turndown
applications (40:1). A 2 in. W.C. p can be applied for sizing if a lower turndrown (in the range of 10:1) is required.Sizing the FRG/6 using a 1 in. W.C. p or less is not recommended for most applications.
-
7/27/2019 Tcv-3035 Horno Regeneracion
9/9