Simulación frigorifico

download Simulación frigorifico

of 10

Transcript of Simulación frigorifico

  • 8/16/2019 Simulación frigorifico

    1/10

    Transient simulation of a two-door frost-free refrigerator subjected toperiodic door opening and evaporator frostingq

    Bruno N. Borges a, Cláudio Melo a, Christian J.L. Hermes b,⇑

    a POLO Research Laboratories for Emerging Technologies in Cooling and Thermophysics, Department of Mechanical Engineering, Federal University of Santa Catarina,

    88040900 Florianópolis, SC, Brazilb Laboratory of Thermodynamics and Thermophysics, Department of Mechanical Engineering, Federal University of Paraná, 81531990 Curitiba, PR, Brazil

    h i g h l i g h t s

    Transient behavior of a refrigerator under periodic door opening is simulated.

     The refrigeration loop is modeled following a semi-empirical quasi-steady approach.

     Energy and moisture transfer into and within the compartments are modeled.

     Key heat and mass transfer parameters were derived from in-house experiments.

     Predictions followed closely the experimental trends for power and temperatures.

    a r t i c l e i n f o

     Article history:

    Received 15 September 2014

    Received in revised form 20 January 2015

    Accepted 21 January 2015

    Available online 17 March 2015

    Keywords:

    Household refrigerator

    Transient simulation

    Door opening

    Evaporator frosting

    a b s t r a c t

    This paper describes a quasi-steady-state simulation model for predicting the transient behavior of a

    two-door household refrigerator subjected to periodic door opening and evaporator frosting. A semi-

    empirical steady-state model was developed for the refrigeration loop, whereas a transient model was

    devised to predict the energy and mass transfer into and within the refrigerated compartments, and also

    the frost build-up on the evaporator. The key empirical heat and mass transfer parameters required by

    the model were derived from a set of experiments performed in-house in a climate-controlled chamber.

    In general, it was found that the model predictions followed closely the experimental trends for the

    power consumption (deviations within ±10%) and for the compartment temperatures (deviations within

    ±2 K) when the doors are opened periodically and frost is allowed to accumulate over the evaporator.

     2015 Elsevier Ltd. All rights reserved.

    1. Introduction

    Modern refrigerator design is aimed at energy savings and also

    at product robustness in relation to evaporator frosting. In this

    regard, standardized tests [1,2] as well as tests under real usage

    conditions, that is, with doors opened regularly   [3,4]   allowing

    moisture to enter the refrigerated compartment and frost to

    accumulate on the evaporator [5]  are procedures commonly car-

    ried out by most manufacturers.

    Nevertheless, since the experimental procedures for frost-free

    refrigerators and freezers are costly and time consuming  [6,7],

    simulation models have been devised to improve the product

    development process [8–15]. None of them, however, can predict

    the refrigerator performance degradation due to periodic door

    opening and consequent evaporator frosting.

    Recently, Mastrullo et al.   [16]   put forward a transient sim-

    ulation model that is suitable to predict the time evolution of the

    compartment air temperature and the power consumption taking

    into account the door opening, and the resulting evaporator frost-

    ing. The model was developed and validated for a single-door

    upright freezer, which represents a small niche in the realm of 

    household refrigeration if compared with two-door frost-free

    appliances, the so-called ‘‘Combi’’ refrigerators [11,14].

    To the best of the authors’ knowledge, none of the models avail-

    able in the literature [8–16] are able to predict the performance of 

    two-door frost-free refrigerators under periodic door opening,

    which not only affect the sensible and the latent loads, but also

    allows frost to build-up on the evaporator, thus decreasing the

    air flow rate supplied by the fan.

    To advance a simulation model for predicting the transient

    behavior of a two-door frost-free refrigerator subjected to periodic

    http://dx.doi.org/10.1016/j.apenergy.2015.01.089

    0306-2619/  2015 Elsevier Ltd. All rights reserved.

    q An abridged version of this manuscript was presented at the 15th International

    Refrigeration and Air Conditioning Conference at Purdue, July 14–17, 2014.⇑ Corresponding author. Tel./fax: +55 41 3361 3239.

    E-mail address:  [email protected] (C.J.L. Hermes).

    Applied Energy 147 (2015) 386–395

    Contents lists available at  ScienceDirect

    Applied Energy

    j o u r n a l h o m e p a g e :   w w w . e l s e v i e r . c o m / l o c a t e / a p e n e r g y

    http://dx.doi.org/10.1016/j.apenergy.2015.01.089mailto:[email protected]://dx.doi.org/10.1016/j.apenergy.2015.01.089http://www.sciencedirect.com/science/journal/03062619http://www.elsevier.com/locate/apenergyhttp://www.elsevier.com/locate/apenergyhttp://www.sciencedirect.com/science/journal/03062619http://dx.doi.org/10.1016/j.apenergy.2015.01.089mailto:[email protected]://dx.doi.org/10.1016/j.apenergy.2015.01.089http://crossmark.crossref.org/dialog/?doi=10.1016/j.apenergy.2015.01.089&domain=pdf

  • 8/16/2019 Simulación frigorifico

    2/10

    door opening is therefore the main aim of this study. The proposed

    model follows a quasi-steady-state approach  [14], with a steady-

    state sub-model for the refrigeration loop and a transient sub-

    model for the energy and moisture transfer into and within the

    refrigerated compartments. An additional frost growth and den-

    sification sub-model was developed to predict the frost accumula-

    tion on the evaporator over time.

    2. Simulation model

     2.1. Refrigeration loop

    A 433-liter top-mount refrigerator, running with R-134a and

    comprised of a 6.76-cm3 hermetic reciprocating compressor, natu-

    ral draft wire-on-tube condenser, tube-fin evaporator and capillary

    tube-suction line heat exchanger, illustrated in Fig. 1, was adopted

    in this study.

     2.1.1. Compressor 

    The compressor sub-model uses the volumetric (gv) and overall

    (gg) efficiencies to calculate the compression power and the refrig-erant mass flow rate for a given operating condition. The

    compressor shell thermal conductance (UAk) is also required for

    the heat transfer calculation [12]. The refrigerant specific enthalpy

    at the compressor outlet is thus obtained from the following

    energy balance [13]:

    h2 ¼  h1 þ h2;s  h1

    gg UAkðT 2  T aÞ

    mkð1Þ

    Nomenclature

    Roman A   heat transfer area, m2

    C    thermal capacity, J K1

    c p   specific heat at constant pressure, J kg1 K1

    D   inner diameter, mDfr   effective vapor diffusivity in frosted media, m2 s

    1

    G   mass flux, kg/m2 sH    height, mh   specific enthalpy, J kg1

    Ha Hatta number, dimensionlesshlv   latent heat of evaporation, J kg

    1

    hsv   latent heat of sublimation, J kg1

    k   thermal conductivity, W m1 K1

    kfr   effective thermal conductivity in frosted media,W m1 K1

    L   length, mLe Lewis number, dimensionlessm   mass flow rate, kg s1

    N    compressor speed, HzNTU number of transfer units, dimensionless p   pressure, PaQ    heat transfer rate, Wr    air flow ratio, dimensionlessS    compressor swept volume, m3

    T    temperature, KUA thermal conductance, Wv   specific volume, m3 kg1

    V    volumetric air flow rate, m3 s1

    W    compression power, Ww   humidity ratio, kgv kga

    1

    W    width, m

    Greeka   heat transfer coefficient, W m2 K1

    d   frost thickness, mec   emissivity of the condenser wall, dimensionlessex   heat exchanger effectiveness, dimensionless/   correction factor, kgvD p   pressure drop, Pa

    Dt    time-step, sgg   global compression efficiency, dimensionlessgv   volumetric compression efficiency, dimensionlessq   density, mr   Stefan-Boltzmann constant, W m2 K4

    f   evaporator dry-out position, m

    Subscripts1 compressor inlet2 condenser inlet3 condenser outlet4 evaporator inlet5 evaporator outleta ambient, airc condensercap capillary tubed doore evaporatorf flash-pointff fresh-foodfr frostfz freezerg saturated vapor at the evaporating pressurei inletk compressorl saturated liquidlat latent thermal loadm mulliono outletr refrigerants isentropic processsat saturationsen sensible thermal loadss steady-statesub subcoolingsuc suction linesup superheatingv saturated vaporx internal heat exchanger

    Fig. 1.  Schematic representation of the refrigeration loop.

    B.N. Borges et al. / Applied Energy 147 (2015) 386–395   387

    http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/16/2019 Simulación frigorifico

    3/10

    where (h2,s–h1)/gg   is the compression power, whereas the massflow rate displaced by the compressor,   mk, is calculated from

    [12,13]:

    mk  ¼  gvNS 

    v 1

    ð2Þ

    where  N   and S  are the compressor speed and the swept volume,

    respectively. The compression efficiencies were fitted to the experi-

    mental data as linear functions of the pressure ratio, and the UAkcoefficient was expressed as a linear fit to the surrounding air tem-

    perature data [12,13].

     2.1.2. Capillary tube suction line heat exchanger 

    The internal heat exchanger was modeled according to the

    semi-empirical approach introduced by Hermes et al.   [17], who

    considered the refrigerant flow and the heat transfer as indepen-

    dent phenomena, and derived explicit algebraic expressions for

    the refrigerant mass flow rate as follows:

    mxmad

    ¼ 1:29  LsucLcap

    0:145DsucDcap

    0:315e0:285x

    v f lf v glg

    !0:214ð3Þ

    where mad is the mass flow rate of an adiabatic capillary tube withthe same bore and length, calculated as follows:

    mad ¼  6:0

     ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi ffiffiffiffiffiffiffiffiffiffiffiffiffiD5capLcap

     pc  pf v f 

    þ pf    pe g 

      þ  f 

     g 2ln  gpe þ f 

     gpf  þ  f 

    s   ð4Þ

    where  f  = v f  pf k,  g  = v f (1k), and  k = 1.67 105 pf 

    0.72 [17],   v f   and pf are the specific volume and pressure at the flash-point, respectively,

    whereas pc  and  pe  stand for the condensing and evaporating pres-

    sures. The correlation is valid for internal heat exchangers with

    capillary tube inner diameters ranging from 0.553mm to

    2.154 mm, and tube lengths from 2 m to 4 m [17].

    The specific enthalpy at the evaporator inlet and the tempera-

    ture at the compressor inlet are thus expressed as:

    h4 ¼  h3  exc p;1ðT 3  T 5Þ ð5Þ

    T 1 ¼  T 5 þ exðT 3  T 5Þ ð6Þ

    where   ex = NTU/(1 + NTU) is the heat exchanger effectiveness

    (0.65), whereas NTU stands for the number of transfer units, cal-

    culated as follows [17]:

    NTU ¼  1:4m0:57ad   Lsuc

    D0:43suc

    k2=3g

    l0:1g   c 2=3p;g

    ð7Þ

     2.1.3. Condenser 

    The natural draft wire-and-tube condenser was divided into

    three domains, namely superheating, saturation and subcooling

    [12–14]. The overall heat transfer in the condenser is therefore cal-culated from:

    Q c  ¼  Q c; sup þ Q c;sat þ Q c;sub ¼  UAcðT c  T aÞ ð8Þ

    where T c is the condensing temperature, calculated implicitly by the

    model thus ensuring that the same amount of mass flows through

    the compressor and the capillary tube, whereas  T a  is the surround-

    ing air temperature, which is an input data with a constant value.

    The specific refrigerant enthalpy at the condenser outlet is

    expressed as:

    h3 ¼  h2  Q cmk

    ð9Þ

    As the heat transfer is governed by free convection and radiation on

    the air-side, the thermal conductance was approximated asUAc (ac + arad) ( At + Aw)   [12–14]. The combined heat transfer

    coefficient was calculated from the correlation proposed by Melo

    and Hermes [18],

    ac þaradarad

    ¼5:68  Aw At þ Aw

    0:60 pt dtdt

    0:28 pw dwdt

    0:492T c T aT c þT a

    0:08ð10Þ

    where  dt   and dw  are the tube and wire diameters, respectively,  pt

    and pw  are the tube and wire pitches, respectively, and  At   and Aware the overall heat transfer surface due to the tubes and the wires,

    respectively. The correlation is valid for wire-and-tube condensers

    with tube outer diameter ranging from 4.8 to 6.2 mm, number of 

    tube rows from 13 to 25, and number of wire pairs from 10 to 90

    [18]. The radiative heat transfer coefficient is calculated from the

    following linearized model:

    arad ¼  ecrðT c þ T aÞðT 2c  þ  T 

    2aÞ ð11Þ

    where r is the Stefan–Boltzmann constant, whereas ec (=0.81) is theemissivity of the condenser walls.

     2.1.4. Evaporator 

    The no-frost evaporator, illustrated in  Fig. 2, was divided into

    two domains, namely refrigerant flow and air-side heat and masstransfer. The specific refrigerant enthalpy at the evaporator outlet

    can be expressed as [12–14]:

    h5 ¼  h4 þ Q sen þ Q lat

    mxð12Þ

    where  h5 = h( pe,  T 5) and  T 5 = T e + DT sup. The evaporator superheat-

    ing,  DT sup, varies with time due to the periodic door opening. To

    address this issue, a moving-boundary approach, as introduced by

    Wedekind and Stoecker [19], was adopted:

    f ¼  fss  ðfss  f

    Þ expðsDt Þ ð13Þ

    where   fss  is the two-phase boundary position in the steady-state

    regime, and s   is a time constant, calculated respectively from

    fss ¼ ð1  x4Þmoxhlvq0

      ð14Þ

    s ¼ ð1 cÞqlð

    14pD2eÞhlv

    q0  ð15Þ

    where   mxo (=3.8 kg/h) is the initial mass flow rate evaluated at

    steady-state conditions,   c   is the mean void fraction of the two-phase region, calculated as suggested by Cioncolini and Thome

    [20],  De   is the inner diameter of the evaporator coil, and  q0 is the

    heat transfer rate per unit length in the two-phase region, calcu-

    lated from

    q0 ¼ mxðhv  h4Þ

    fo  ð16Þ

    where  f = Le  at  t  = 0.

    Fig. 2.  Schematic representation of the ‘‘no-frost’’ evaporator coil.

    388   B.N. Borges et al./ Applied Energy 147 (2015) 386–395

  • 8/16/2019 Simulación frigorifico

    4/10

     2.2. Evaporator frosting 

    The evaporator sub-model calculates the cooling capacity from

    the following heat and mass balances on the air-side (see Fig. 2). In

    the case of a uniform coil temperature, i.e. evaporator filled with

    two-phase refrigerant, the heat and mass balances yield:

    Q sen ¼  mac p;aðT fr  T iÞ   1 exp     ae Aemac p;a

      ð17Þ

    Q lat ¼  mahsvðwfr  wiÞ   1 exp     ae Ae

    mac p;aLe

    2=3 !" #   ð18Þwhere   Q e = Q sen + Q lat,   T fr   is the frost surface temperature,

    wfr = wsat(T fr) is the humidity ratio at the frost surface, Le is the

    Lewis number and ae  is the air-side heat transfer coefficient calcu-lated as suggested by Barbosa et al.  [21],

    aeGmaxc p

    ¼ 0:6976 Re0:4842D Ae Ato

    0:3426Pr2=3 ð19Þ

    where  Gmax = ma/ Amin   is the mass flux at the minimum free flow

    passage, i.e. the cross-section area obtained from a transversal cut

    including tubes and fins, and Ato is the surface area of the tube only.

    One should note that the evaporator of the refrigerator under study

    is similar to sample #6 tested by Barbosa et al. [21]. In addition, one

    should note that, in the cases where superheated refrigerant takes

    place, the terms between brackets in equations  (17) and (18) must

    be modified to account for the refrigerant temperature variation, as

    described in [22].

    The frost formation model was based on the work of Hermes

    et al. [23], which was originally developed for horizontal flat sur-

    faces and later adapted by  [5]  for finned-tube heat exchangers

    (Fig. 2). According to [23], the frost surface temperature is calcu-

    lated from:

    T fr  ¼  T e þ ðQ sen þ Q latÞd

    kfr Aeþ wsat;ehsvqaDfr

    kfrð1 coshHaÞ ð20Þ

    where Ha is the Hatta number, and kfr and Dfr  are the effective ther-

    mal conductivity and vapor diffusivity of the frost layer, respec-

    tively, calculated as described in [23]. In addition, the growth rate

    of the frost layer of thickness  d  is calculated from:

    dd

    dt ¼

      2kfrbqfrdhsv

     ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi1 þ bdQ senkfr Ae

    2þ4bdhsvkfr

    Gfr

    s     1 þ

     bdQ senkfr Ae

    2435

    ð21Þ

    where   Gfr   is the total mass flux of the vapor transferred to the

    frosted medium, and  b  is an empirical parameter that comes from

    the frost density correlation in the following form  [24]:

    Fig. 3.  Schematic representation of the air flow during a door opening event.

    0,000 0,002 0,004 0,006 0,008 0,010 0,01240

    42

    44

    46

    48

    50

    52

    54

    56

    58

    60

          ∆   P   t

       [   P  a   ]

    Va [m³/s]

    ∆Pe = 5 Pa∆Pe = 5 Pa

    ∆Pe = 15 Pa∆Pe = 15 Pa

    ∆Pe = 25 Pa∆Pe = 25 Pa

    ∆Pe = 35 Pa∆Pe = 35 Pa∆Pe = 45 Pa∆Pe = 45 Pa

    Fig. 4.  Characteristic curve of the fan.

    Fig. 5.  Schematic representation of the wind-tunnel facility.

    B.N. Borges et al. / Applied Energy 147 (2015) 386–395   389

    http://-/?-http://-/?-http://-/?-http://-/?-

  • 8/16/2019 Simulación frigorifico

    5/10

    qfr  ¼  a expðbTfrÞ ð22Þ

    The accumulated frost mass and the frost thickness are calculated,

    respectively, from   mfr = mfro + Gfr AeDt   and   d = d

    o + (dd/dt )Dt   [5,23].

    In addition, the frost density is obtained from qfr(t  > 0) = mfro / Aed

    o,

    where the superscript ()o represents the values at the previous

    time-step. The defrost process has not been accounted for by the

    model.

     2.3. Refrigerated compartments

    The model for the refrigerated compartments, which was based

    on the work of Borges et al.  [14], is aimed at determining the psy-

    chrometric conditions of the moist air inside the fresh-food and

    freezer (frozen-food) compartments over time by means of tran-

    sient energy and mass balances, which yield the following expres-

    sions for the air temperature and humidity of the fresh-food and

    freezer compartments, respectively:

    T   ¼  T ss;  ðT ss;  T oÞ exp  

     ADt 

      ð23Þ

    w  ¼  wss;  ðwss;  woÞ exp   B

    Dt q/

      ð24Þ

    where   T o

      and   wo

      are the air temperature and humidity ratio

    of the compartment at the beginning of the time-step,

     A⁄

     = UA⁄

     + UAm + md,⁄c p,a + m⁄c p,a and  B⁄ = md,⁄ + m⁄. The asterisk ()⁄indicates either the freezer (fz) or the fresh-food (ff) compartment.

    The thermal conductance of each compartment, UA⁄

    , and of the

    mullion, UAm, and the equivalent thermal capacity and mass of each

    compartment,   C ⁄

      and   /⁄, respectively, were all obtained from

    experimental data. In addition, the terms  T ss,⁄  and  wss,⁄  are related

    to the steady-state condition, and calculated as follows:

    T ss;  ¼ ðUA þ md;c p;aÞT a þ UAmT r þ ma;c p;aT o

     A

    ð25Þ

    wss;  ¼ md;wa  mwo

    Bð26Þ

    where

    T o ¼  rTfz þ ð1  r ÞT ff    Q senmac p;a

    ð27Þ

    wo ¼  rwfz þ ð1  r Þwff    Q latmahsv

    ð28Þ

    where r  is the freezer air flow ratio.

    The air flow rate entering the cabinet during a door opening

    event is calculated as described by Wang   [25], and shown in

    Fig. 3, as follows:

    md; ¼ 2

    3K qW d;H d;

     ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi ffiffi2gHd;ð1 qa=qÞ

    ð1 þ ðq=qaÞ1=3Þ

    3

    v uut   ð29Þwhere   K ⁄ is an empirical discharge coefficient determined from

    experimental data.

    The air-side hydrodynamics was modeled according to the

    methodology outlined in Hermes et al.   [13]. The overall pressure

    drop was thus correlated to the air flow rate through the following

    expression:

    D pt ¼  c qaV 2 þ D pe   ð30Þ

    where c is an empirical coefficient obtained from experimental data,

    and D pe is the pressure drop in the frosted evaporator, calculated asfollows:

    D p ¼

     fG2max

    2qa

     Ae Amin ð31Þ

    where f  is the friction factor calculated from  [21]:

     f   ¼ 5:965 Re0:2948D Ae At

    0:7671N lo2

    0:4436ð32Þ

    The characteristic curve for the fan, depicted in Fig. 4, wasfitted toa

    third-order polynomial using experimental data obtained in a wind-

    tunnel facility [13], illustrated in Fig. 5.

     2.4. Solution algorithm

    The model was coded in EES [26]. The solution algorithm, illus-

    trated in Fig. 6, is based on a sequential solution for the models forthe refrigerated compartments and the refrigeration loop, whose

    Fig. 6.  Information flow diagram of the simulation model.

    390   B.N. Borges et al./ Applied Energy 147 (2015) 386–395

  • 8/16/2019 Simulación frigorifico

    6/10

    sub-models are in turn solved simultaneously by the Newton–

    Raphson technique. The evaporator frosting and dry-out sub-mod-

    els are solved implicitly in the inner loop, whereas the models for

    the refrigerated compartments are solved explicitly in an outer

    loop, as depicted in  Fig. 6. The on–off cycles were implemented

    by means of an IF-THEN-ELSE loop that emulates a thermostat.

    The door opening patterns are included in the model in an outer

    loop, as shown in Fig. 6. More information can be obtained in [22].

    3. Experimental work 

    The refrigerator was carefully instrumented as illustrated in

    Fig. 7. The evaporating and condensing pressures were measured

    by means of strain gauge pressure transducers ranging from 0 to

    10 bar (±2 mbar uncertainty) and from 0 to 20 bar (±4 mbar uncer-

    tainty), respectively. A Coriolis-type mass flow meter with a mea-

    surement uncertainty of ±0.03 kg/h was installed at the

    compressor discharge. The compressor and fan power consump-

    tion were monitored using a digital power analyzer with a mea-

    surement uncertainty of ±0.1%. Capacitive relative humidity

    transducers (±2% uncertainty) were installed at the evaporator

    inlet and outlet together with pressure takes for air-side pressure

    drop measurements using a differential pressure transducer rang-ing from 0 to 62.5Pa (±0.3 Pa uncertainty). All   T -type

    thermocouples employed in this study have a measurement uncer-

    tainty of ±0.3 C. More details can be found in  [22].

    The experimental plan, summarized in Table 1, was designed to

    provide all of the empirical information required for the sake of 

    model closing. The doors were opened and closed using a pur-

    pose-built door-opening device attached to both the freezer and

    fresh-food doors [3], so that they could be operated independently.

    The arrangement is placed within a climate chamber, depicted in

    Fig. 8, which provides a strict control of temperature, humidity

    and air velocity.The time between door opening events and the length of time of 

    the event are both easily programmed. Patterns comprised of 4

    cycles of door opening events, each cycle lasting 1 h and applied

    in sequence, were adopted, with a 4-h interval between cycles.

    After this period, the system was kept running for 8 h with the

    doors closed. The pattern was repeated every 24 h. In a door open-

    ing cycle, the freezer door was opened every 12 min for 10 s over a

    period of 1 h, totalizing 5 opening events per hour. On the other

    hand, the fresh-food door was opened every 2.5 min for 30 s, tota-

    lizing 20 opening events per hour.

    4. Results

    The model predictions were compared with the correspondingexperimental data for ambient conditions of 32 C and 70% RH.

    Fig. 7.  Summary of the instrumentation.

     Table 1

    Summary of experimental tests.

    Experiment Test facility Ambient conditions Empirical parameter

    Fan characteristics Wind-tunnel 21 C, 50% RH 3rd-order polynomial

    Cabinet hydrodynamics Wind-tunnel 21 C, 50% RH   c Refrigeration loop Chamber 6 runs, doors closed, 25 < T  < 38 C, 8 < w < 32g/kg   r , gv, gg, UAk, UA⁄, UAm,  C ⁄Door opening tests Chamber 3 runs, door openings, 25 < T  < 38 C, 12 < w < 21g/kg   K ⁄,  /⁄, qfr

    o , mko, b

    B.N. Borges et al. / Applied Energy 147 (2015) 386–395   391

    http://-/?-http://-/?-http://-/?-

  • 8/16/2019 Simulación frigorifico

    7/10

    The simulations were initiated at the compressor start up immedi-

    ately after a defrost cycle and lasted until the next defrost cycle

    began.   Fig. 9   shows the predicted and experimental results for

    the refrigerated compartment temperatures for the whole period.

    Two door opening cycles can be clearly seen, the first from  30

    to  90 min and the second from  330 to  390 min. It should be

    noted that the model follows closely the experimental trends, with

    an average deviation of around ±2 C, the maximum discrepancies

    occurring during door opening.

    Fig. 10 compares the predictions of the working pressures with

    the experimental data. It can be observed that the model predic-

    tions for the evaporating pressure are within a ±5% error band,

    while the condensing pressure is under predicted with an offset

    of approximately 0.5 bar during the whole period, but with devia-

    tions within a ±10% band. Consequently, the power consumption is

    also reasonably well predicted by the model, with deviations not

    exceeding ±5%, as shown in Fig. 11.

    Fig. 12 shows the time-evolution of the evaporator superheat-

    ing. Five peaks can be observed during the test period, which

    Fig. 8.  Schematic representation of the climate chamber.

    0 60 120 180 240 300 360 420 480 540

    -25

    -20

    -15

    -10

    -5

    0

    5

    10

    15

    20

    25

    Time [min]

    Tfz, Experimental

    Tfz, Simulated

    Tff, Experimental

    Tff, Simulated

       T  e  m  p  e  r  a   t  u  r  e   [   °   C   ]

    Fig. 9.  Time evolution of the refrigerated compartment temperatures.

    0 60 120 180 240 300 360 420 480 5407

    8

    9

    10

    11

    12

    13

    14

    15

    16

    17

    0.7

    0.8

    0.9

    1.0

    1.1

    1.2

    1.3

    1.4

    1.5

    1.6

    1.71.8

    1.9

    2.0

    Time [min]

       E  v  a  p  o  r  a   t   i  n  g  p  r  e  s  s  u  r  e   [   b  a  r   ]

       C  o  n   d  e  n  s   i  n  g  p  r  e  s  s  u  r  e   [   b  a  r   ]

    Pc, Experimental Pc, SimulatedPc, Simulated

    Pe, ExperimentalPe, Exper imen tal Pe, SimulatedPe, Simulated

    Fig. 10.  Time evolution of the condensing and evaporating pressures.

    392   B.N. Borges et al./ Applied Energy 147 (2015) 386–395

  • 8/16/2019 Simulación frigorifico

    8/10

    appear when both doors are opened concurrently, thus increasing

    the thermal loads and pushing the dry-out position downstream of 

    the evaporator. Small variations in the evaporator superheating

    occur when only the door of the fresh-food compartment is

    opened. It can also be noted that the model predictions follow

    the experimental trends satisfactorily, although errors of up to

    3 K can be observed in the peaks.

    Fig. 13 shows the time-evolution of the air-side pressure drop

    due to evaporator frosting and Fig. 14 explores the air-side predic-

    tion capabilities of the model. For a clean evaporator coil, a 5 Pa

    pressure drop is observed, increasing steadily to 15 Pa during the

    first cycle of door opening events. This value does not change dur-

    ing the period when the doors are kept closed, since there is no

    moisture infiltration and, therefore, no frost growth. During the

    second cycle of door openings the evaporator air-side pressure

    drop increases to around 25 Pa. During the whole period the model

    predicted satisfactorily the experimental trends, although absolute

    errors of up to 5 Pa can be observed.

    Fig. 14 shows the calculated frost mass for each of the five evap-

    orator rows. The rows are numbered from bottom to top, according

    to the air flow direction, as illustrated in Fig. 2, and comprised 27

    (1st), 34 (2nd), 67 (3rd), 66 (4th), and 67 (5th) fins. It can be noted

    that the frost is mostly accumulated along the first three rows,

    which is due to the higher humidity gradient at the evaporator

    inlet. It can also be noted that there is more frost accumulated

    along the 3rd row than along the 1st row, which is due to thehigher heat transfer (finned) area of the former.

    0 60 120 180 240 300 360 420 480 540

    0

    20

    40

    60

    80

    100

    120

    140

    160

    180

    200

    Time [min]

       C  o  m  p  r  e  s  s   i  o  n  p  o  w  e  r   [   W   ]

    SimulatedSimulated

    ExperimentalExperimental

    Fig. 11.  Time evolution of the compression power.

    0 60 120 180 240 300 360 420 480 540

    0

    2

    4

    6

    8

    10

    12

    Time [min]

       E  v  a  p  o  r  a   t  o  r  s  u  p

      e  r   h  e  a   t   i  n  g   [   K   ]

    Experimental

    SimulatedSimulated

    Fig. 12.  Time evolution of the evaporator superheating.

    0 60 120 180 240 300 360 420 480 540

    0

    5

    10

    15

    20

    25

    30

    Time [min]

    Experimental

    SimulatedSimulated

       E  v  a  p  o  r  a   t  o  r  a   i  r  -  s   i   d  e  p  r  e  s  s  u  r  e   d  r  o  p   [   P  a   ]

    Fig. 13.  Time evolution of the evaporator air-side pressure drop.

    0 60 120 180 240 300 360 420 480 540

    0

    20

    40

    60

    80

    100

    120

    Time [min]

       A  c  c  u  m  u   l  a   t  e   d   f  r  o

      s   t  m  a  s  s   [  g   ]

    2nd

    Row2nd

    Row

    1st Row

    3rd

    Row3rd

    Row

    4th

    Row4th

    Row

    5th

    Row5th

    Row

    Fig. 14.  Time evolution of the accumulated frost mass along each evaporator row.

    B.N. Borges et al. / Applied Energy 147 (2015) 386–395   393

    http://-/?-http://-/?-

  • 8/16/2019 Simulación frigorifico

    9/10

    5. Summary and conclusions

    A quasi-steady-state semi-empirical mathematical model was

    developed to predict the transient behavior of the key operating

    parameters (i.e., working pressures, compression power, compart-

    ment temperatures, and accumulated frost mass on the evap-

    orator) of a two-door frost-free refrigerator subjected to periodic

    door opening. The model predictions were compared with a setof in-house experimental data collected in a climate-controlled

    chamber. The door opening were carried out by a purpose-built

    apparatus according to a predefined pattern.

    It was found that the model predictions followed closely the

    experimental trends, with deviations for the working pressures

    and power consumption not exceeding the 10% thresholds and pre-

    dictions for the compartment air temperatures being within ±2 C

    error bands. The model was also used to predict the frost dis-

    tribution over the evaporator coil and it was observed that the frost

    accumulates mostly in the first three rows, the third row being cru-

    cial in terms of frost clogging because of the higher number of fins

    and thus lower free flow passage of air.

     Acknowledgments

    This study was carried out at the POLO facilities under National

    Grant No. 573581/2008-8 (National Institute of Science and

    Technology in Refrigeration and Thermophysics) funded by the

    Brazilian Government Agency CNPq. The authors are grateful to

    Mr. Rafael Gões for his valuable support in the experiments.

    Financial support from Whirlpool Latin America S.A. is also duly

    acknowledged.

     Appendix A. Refrigerator characteristics

    Refrigerator 

    Type: Top-mount frost-free.

    Refrigerant type/charge: HFC-134a/100 g.

    Cabinet internal volume: 439 liters.

    Fan power consumption: 7 W.

    Compressor 

    Type: Hermetic reciprocating compressor.

    Stroke: 6.76 cm3.

    Speed: 60 Hz.

    Condenser 

    Type/material: wire-and-tube/steel.

    Length of the discharge line: 1600 mm.

    Condenser height/length of the wires: 1210 mm.Condenser width: 540 mm.

    Tube outer diameter: 5.1 mm.

    Bend radius: 28.8 mm.

    Number of tubes: 21.

    Wire diameter: 1.4 mm.

    Number of wires: 90.

    Surface emissivity: 0.81.

    Internal heat exchanger 

    Type/material: concentric/copper.

    Capillary tube outer diameter: 1.90 mm.

    Capillary tube inner diameter: 0.80 mm.

    Capillary tube length: 2.55 m.

    Heat exchanger length: 1.34 m.

    Approximate heat exchanger effectiveness: 65%.

    Suction line inner diameter: 7 mm.

    Evaporador 

    Type/material: no-frost tube-fin/aluminium.

    Coil length: 7.585 m.Inner diameter: 6.7 mm.

    Outer diameter: 7.9 mm.

    Number of tubes: 10 (longitudinal)/2 (transversal).

    Evaporator height: 189 mm.

    Evaporator width: 340 mm.

    Evaporator depth: 59 mm.

    Number of fins (1st row): 27.

    Number of fins (2nd row): 34.

    Number of fins (3rd row): 67.

    Number of fins (4th row): 66.

    Number of fins (5th row): 67.

    Fin dimensions: 35 mm (height)/59 mm (width)/0.125 mm

    (thickness).

    References

    [1]  Bansal PK. Developing new test procedures for domestic refrigerators:

    harmonisation issues and future R&D needs—a review. Int J Refrig

    2003;26:735–48.

    [2] Mahlia TMI, Saidur R. A review on test procedure, energy efficiency standards

    and energy labels for room air conditioners and refrigerator–freezers. Renew

    Sustain Energy Rev 2010;14:1888–900.

    [3] Piucco RO, Hermes CJL, Melo C. In-situ evaluation of a criterion to predict frost

    formation on liners of refrigerated cabinets. Appl Therm Eng

    2011;31:3084–91.

    [4]  Geppert J, Stamminger R. Analysis of effecting factors on domestic

    refrigerators’ energy consumption in use. Energy Convers Manage

    2013;76:794–800.

    [5]  Knabben FT, Hermes CJL, Melo C. In-situ study of frosting and defrosting

    processes in tube-fin evaporators of household refrigerating appliances. Int J

    Refrig 2011;34:2031–41.

    [6]  Negrão COR, Hermes CJL. Energy and cost savings in household refrigerating

    appliances: a simulation-based design approach. Appl Energy

    2011;88:3051–60.

    [7] Hermes CJL, Melo C, Knabben FT. Alternative test method to assess the energy

    performance of frost-free refrigerating appliances. Appl Therm Eng

    2013;50:1029–34.

    [8] Chen ZJ, Lin W-H. Dynamic simulation and optimal matching of a small-scale

    refrigeration system. Int J Refrig 1991;14:329–35.

    [9] Jansen MJP, de Wit JA, Kuijpers LJM. Cycling losses in domestic appliances: an

    experimental and theoretical analysis. Int J Refrig 1992;15:152–8.

    [10]   Ploug-Sørensen L, Fredsted JP, Willatzen M. Improvements in the modelling

    and simulation of refrigeration systems: aerospace tools applied to a domestic

    refrigerator. J HVAC&R Res 1997;3:387–403.

    [11]   Hermes CJL, Melo C. A first-principles simulation model for the start-up and

    cycling transients of household refrigerators. Int J Refrig 2008;31:1341–57.

    [12]  Gonçalves JM, Melo C, Hermes CJL. A semi-empirical model for steady-state

    simulation of household refrigerators. Appl Therm Eng 2009;29:1622–30.[13]   Hermes CJL, Melo C, Knabben FT, Gonçalves JM. Prediction of the energy

    consumption of household refrigerators and freezers via steady-state

    simulation. Appl Energy 2009;86:1311–9.

    [14]   Borges BN, Hermes CJL, Goncalves JM, Melo C. Transient simulation of 

    household refrigerators: a semi-empirical quasi-steady approach. Appl

    Energy 2011;88:748–54.

    [15]   Mitishita RS, Barreira EM, Negrão COR, Hermes CJL. Thermoeconomic design

    and optimization of frost-free refrigerators. Appl Therm Eng

    2013;50:1376–85.

    [16]  Mastrullo R, Mauro RW, Menna L, Palma A, Vanoli GP. Transient model of a

    vertical freezer with door openings and defrost effects. Appl Energy

    2014;121:38–50.

    [17]  Hermes CJL, Melo C, Knabben FT. Algebraic solution of capillary tube flows.

    Part II: capillary tube suction line heat exchangers. Appl Therm Eng

    2010;30:770–5.

    [18]  Melo C, Hermes CJL. A heat transfer correlation for the natural draft wire-and-

    tube condensers. Int J Refrig 2009;32:546–55.

    [19]  Wedekind GL, Stoecker WF. Theoretical model for predicting the transient

    response of the mixture-vapor transition point in horizontal evaporating flow. J Heat Transfer 1968;90:165–74.

    394   B.N. Borges et al./ Applied Energy 147 (2015) 386–395

    http://refhub.elsevier.com/S0306-2619(15)00125-7/h0005http://refhub.elsevier.com/S0306-2619(15)00125-7/h0005http://refhub.elsevier.com/S0306-2619(15)00125-7/h0005http://refhub.elsevier.com/S0306-2619(15)00125-7/h0010http://refhub.elsevier.com/S0306-2619(15)00125-7/h0010http://refhub.elsevier.com/S0306-2619(15)00125-7/h0010http://refhub.elsevier.com/S0306-2619(15)00125-7/h0015http://refhub.elsevier.com/S0306-2619(15)00125-7/h0015http://refhub.elsevier.com/S0306-2619(15)00125-7/h0015http://refhub.elsevier.com/S0306-2619(15)00125-7/h0020http://refhub.elsevier.com/S0306-2619(15)00125-7/h0020http://refhub.elsevier.com/S0306-2619(15)00125-7/h0020http://refhub.elsevier.com/S0306-2619(15)00125-7/h0025http://refhub.elsevier.com/S0306-2619(15)00125-7/h0025http://refhub.elsevier.com/S0306-2619(15)00125-7/h0025http://refhub.elsevier.com/S0306-2619(15)00125-7/h0030http://refhub.elsevier.com/S0306-2619(15)00125-7/h0030http://refhub.elsevier.com/S0306-2619(15)00125-7/h0030http://refhub.elsevier.com/S0306-2619(15)00125-7/h0035http://refhub.elsevier.com/S0306-2619(15)00125-7/h0035http://refhub.elsevier.com/S0306-2619(15)00125-7/h0035http://refhub.elsevier.com/S0306-2619(15)00125-7/h0040http://refhub.elsevier.com/S0306-2619(15)00125-7/h0040http://refhub.elsevier.com/S0306-2619(15)00125-7/h0045http://refhub.elsevier.com/S0306-2619(15)00125-7/h0045http://refhub.elsevier.com/S0306-2619(15)00125-7/h0050http://refhub.elsevier.com/S0306-2619(15)00125-7/h0050http://refhub.elsevier.com/S0306-2619(15)00125-7/h0050http://refhub.elsevier.com/S0306-2619(15)00125-7/h0055http://refhub.elsevier.com/S0306-2619(15)00125-7/h0055http://refhub.elsevier.com/S0306-2619(15)00125-7/h0060http://refhub.elsevier.com/S0306-2619(15)00125-7/h0060http://refhub.elsevier.com/S0306-2619(15)00125-7/h0060http://refhub.elsevier.com/S0306-2619(15)00125-7/h0065http://refhub.elsevier.com/S0306-2619(15)00125-7/h0065http://refhub.elsevier.com/S0306-2619(15)00125-7/h0065http://refhub.elsevier.com/S0306-2619(15)00125-7/h0070http://refhub.elsevier.com/S0306-2619(15)00125-7/h0070http://refhub.elsevier.com/S0306-2619(15)00125-7/h0070http://refhub.elsevier.com/S0306-2619(15)00125-7/h0075http://refhub.elsevier.com/S0306-2619(15)00125-7/h0075http://refhub.elsevier.com/S0306-2619(15)00125-7/h0075http://refhub.elsevier.com/S0306-2619(15)00125-7/h0080http://refhub.elsevier.com/S0306-2619(15)00125-7/h0080http://refhub.elsevier.com/S0306-2619(15)00125-7/h0080http://refhub.elsevier.com/S0306-2619(15)00125-7/h0085http://refhub.elsevier.com/S0306-2619(15)00125-7/h0085http://refhub.elsevier.com/S0306-2619(15)00125-7/h0085http://refhub.elsevier.com/S0306-2619(15)00125-7/h0090http://refhub.elsevier.com/S0306-2619(15)00125-7/h0090http://refhub.elsevier.com/S0306-2619(15)00125-7/h0095http://refhub.elsevier.com/S0306-2619(15)00125-7/h0095http://refhub.elsevier.com/S0306-2619(15)00125-7/h0095http://refhub.elsevier.com/S0306-2619(15)00125-7/h0095http://refhub.elsevier.com/S0306-2619(15)00125-7/h0095http://refhub.elsevier.com/S0306-2619(15)00125-7/h0095http://refhub.elsevier.com/S0306-2619(15)00125-7/h0095http://refhub.elsevier.com/S0306-2619(15)00125-7/h0090http://refhub.elsevier.com/S0306-2619(15)00125-7/h0090http://refhub.elsevier.com/S0306-2619(15)00125-7/h0085http://refhub.elsevier.com/S0306-2619(15)00125-7/h0085http://refhub.elsevier.com/S0306-2619(15)00125-7/h0085http://refhub.elsevier.com/S0306-2619(15)00125-7/h0080http://refhub.elsevier.com/S0306-2619(15)00125-7/h0080http://refhub.elsevier.com/S0306-2619(15)00125-7/h0080http://refhub.elsevier.com/S0306-2619(15)00125-7/h0075http://refhub.elsevier.com/S0306-2619(15)00125-7/h0075http://refhub.elsevier.com/S0306-2619(15)00125-7/h0075http://refhub.elsevier.com/S0306-2619(15)00125-7/h0070http://refhub.elsevier.com/S0306-2619(15)00125-7/h0070http://refhub.elsevier.com/S0306-2619(15)00125-7/h0070http://refhub.elsevier.com/S0306-2619(15)00125-7/h0065http://refhub.elsevier.com/S0306-2619(15)00125-7/h0065http://refhub.elsevier.com/S0306-2619(15)00125-7/h0065http://refhub.elsevier.com/S0306-2619(15)00125-7/h0060http://refhub.elsevier.com/S0306-2619(15)00125-7/h0060http://refhub.elsevier.com/S0306-2619(15)00125-7/h0055http://refhub.elsevier.com/S0306-2619(15)00125-7/h0055http://refhub.elsevier.com/S0306-2619(15)00125-7/h0050http://refhub.elsevier.com/S0306-2619(15)00125-7/h0050http://refhub.elsevier.com/S0306-2619(15)00125-7/h0050http://refhub.elsevier.com/S0306-2619(15)00125-7/h0045http://refhub.elsevier.com/S0306-2619(15)00125-7/h0045http://refhub.elsevier.com/S0306-2619(15)00125-7/h0040http://refhub.elsevier.com/S0306-2619(15)00125-7/h0040http://refhub.elsevier.com/S0306-2619(15)00125-7/h0035http://refhub.elsevier.com/S0306-2619(15)00125-7/h0035http://refhub.elsevier.com/S0306-2619(15)00125-7/h0035http://refhub.elsevier.com/S0306-2619(15)00125-7/h0030http://refhub.elsevier.com/S0306-2619(15)00125-7/h0030http://refhub.elsevier.com/S0306-2619(15)00125-7/h0030http://refhub.elsevier.com/S0306-2619(15)00125-7/h0025http://refhub.elsevier.com/S0306-2619(15)00125-7/h0025http://refhub.elsevier.com/S0306-2619(15)00125-7/h0025http://refhub.elsevier.com/S0306-2619(15)00125-7/h0020http://refhub.elsevier.com/S0306-2619(15)00125-7/h0020http://refhub.elsevier.com/S0306-2619(15)00125-7/h0020http://refhub.elsevier.com/S0306-2619(15)00125-7/h0015http://refhub.elsevier.com/S0306-2619(15)00125-7/h0015http://refhub.elsevier.com/S0306-2619(15)00125-7/h0015http://refhub.elsevier.com/S0306-2619(15)00125-7/h0010http://refhub.elsevier.com/S0306-2619(15)00125-7/h0010http://refhub.elsevier.com/S0306-2619(15)00125-7/h0010http://refhub.elsevier.com/S0306-2619(15)00125-7/h0005http://refhub.elsevier.com/S0306-2619(15)00125-7/h0005http://refhub.elsevier.com/S0306-2619(15)00125-7/h0005

  • 8/16/2019 Simulación frigorifico

    10/10

    [20]  Cioncolini A, Thome JR. Void fraction predictionin annular two-phase flow. Int

     J Multiphase Flow 2012;43:72–84.

    [21]   Barbosa Jr JR, Melo C, Hermes CJL, Waltrich PJ. A study of the air-side heat

    transfer and pressure drop characteristics of tube-fin no-frost evaporators.

    Appl Energy 2009;89:1484–91.

    [22] Borges BN. Semi-empirical modelling of a frost-free refrigerator subjected to

    door opening (in Portuguese), M.Eng. thesis, Federal University of Santa

    Catarina, Florianopolis, SC, Brazil; 2013. 171p.

    [23]   Hermes CJL, Piucco RO, Melo C, Barbosa Jr JR. A study of frost growth and

    densification on flat surfaces. Exp Therm Fluid Sci 2009;33:371–9 .

    [24]   Hermes CJL. An analytical solution to the problem of frost growth and

    densification on flat surfaces. Int J Heat Transfer 2012;55:7346–51.

    [25] Wang H. Modelling of refrigerating system coupled with a refrigerated room,

    PhD thesis, Delft University of Technology, The Netherlands; 1990

    [26] Klein SA. Engineering equation solver, v. 8.954-3D, F-Chart Software, USA;

    2011.

    B.N. Borges et al. / Applied Energy 147 (2015) 386–395   395

    http://refhub.elsevier.com/S0306-2619(15)00125-7/h0100http://refhub.elsevier.com/S0306-2619(15)00125-7/h0100http://refhub.elsevier.com/S0306-2619(15)00125-7/h0105http://refhub.elsevier.com/S0306-2619(15)00125-7/h0105http://refhub.elsevier.com/S0306-2619(15)00125-7/h0105http://refhub.elsevier.com/S0306-2619(15)00125-7/h0110http://refhub.elsevier.com/S0306-2619(15)00125-7/h0110http://refhub.elsevier.com/S0306-2619(15)00125-7/h9000http://refhub.elsevier.com/S0306-2619(15)00125-7/h9000http://refhub.elsevier.com/S0306-2619(15)00125-7/h9000http://refhub.elsevier.com/S0306-2619(15)00125-7/h9000http://refhub.elsevier.com/S0306-2619(15)00125-7/h0110http://refhub.elsevier.com/S0306-2619(15)00125-7/h0110http://-/?-http://refhub.elsevier.com/S0306-2619(15)00125-7/h0105http://refhub.elsevier.com/S0306-2619(15)00125-7/h0105http://refhub.elsevier.com/S0306-2619(15)00125-7/h0105http://-/?-http://refhub.elsevier.com/S0306-2619(15)00125-7/h0100http://refhub.elsevier.com/S0306-2619(15)00125-7/h0100http://-/?-