GENER. ELCTRICA MVIL CACIQUE CHAIMAHVAC Duct Sizing
for
PDVSA
Prepared By:
VENINCO
Domingo, 21 de Octubre de 2012
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
2/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 2
General Project Data Input
General Project InformationProject file name: D:\ELITE\SALA CONTROL GENER. ELCT.
MVIL CACIQUE CHAIMA.dswProject title: GENER. ELCTRICA MVIL CACIQUE CHAIMADesigned by: CONRAD GOLDSTEINProject date: Lunes, 03 de Septiembre de 2012Project comment: SALA DE CONTROLClient name: PDVSACompany name: VENINCO
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
3/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 3
System 1 "SALA CONTROL" - Input Data - Supply
Project & Default Data Trunks RunoutsMaximum desired velocity (FPM): 2,000 800
Material Reference: Galv Rect Galv RectHeight constraint (in): 16 16Width constraint (in): 0 0Diameter constraint (in): 0 0R-Value of insulation (Sq.ft.F/Btuh): 0.00 0.00Duct shape: Rect. Rect.Sizing method: EF EFNC criteria: N/A 35
Duct System DataMaximum system velocity (FPM): 2,000.0Minimum system velocity (FPM): 650.0Minimum trunk diameter (in): 0.0
Orifice opening interval (in): 0.000Temperature of air leaving coil (F): 55Design room temperature (F): 75Temperature of duct installation space (F): 0Altitude (ft): 262Density (lb/cu.ft): 0.076Friction loss per 100 ft. (in.wg): 0.100Est. st. press. loss of central equip. (in.wg): 0.000Maximum % supply air increase: 0Allow increasing downstream diameters: NoShow diversified trunk flows: NoDuct diameter interval (in): 0.0Whole number dimensions: S
Fan DataFan description: CENT-FORWARD
CURVEDFan static pressure (in.wg): 0.000Fan CFM: 0Fan efficiency: 0Fan RPM: 0Number of blades: 0Fan blast width (in): 0Fan blast height (in): 0Length to first fitting (ft): 0.0
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
4/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 4
System 1 "SALA CONTROL" - Input Data - Return
Project & Default Data Trunks RunoutsMaximum desired velocity (FPM): 2,000 800
Material Reference: Galv Rect Galv RectHeight constraint (in): 16 16Width constraint (in): 0 0Diameter constraint (in): 0 0R-Value of insulation (Sq.ft.F/Btuh): 0.00 0.00Duct shape: Rect. Rect.Sizing method: EF EFNC criteria: N/A 35
Duct System DataMaximum system velocity (FPM): 2,000.0Minimum system velocity (FPM): 650.0Minimum trunk diameter (in): 0.0
Orifice opening interval (in): 0.000Temperature of air leaving coil (F): 75Design room temperature (F): 75Temperature of duct installation space (F): 0Altitude (ft): 262Density (lb/cu.ft): 0.073Friction loss per 100 ft. (in.wg): 0.050Est. st. press. loss of central equip. (in.wg): 0.000Maximum % supply air increase: 0Allow increasing downstream diameters: NoShow diversified trunk flows: NoDuct diameter interval (in): 0.0Whole number dimensions: S
Fan DataFan description: CENT-FORWARD
CURVEDFan static pressure (in.wg): 0.000Fan CFM: 0Fan efficiency: 0Fan RPM: 0Number of blades: 0Fan blast width (in): 0Fan blast height (in): 0Length to first fitting (ft): 0.0
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
5/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 5
System 1 "SALA CONTROL" - Trunk Input Data - Supply
TrunkUps.
SM
DiaHei
Wid
LengthMax.Vel
Fit 1Fit 2
Junc fit
#Fit#Fit
#Fit
ShapeAdd.Loss
R-Value
ActiveTake Off
Per.Div
Material Ref.Roughness
9 0.0 37.96 CR3-1 3 Rect. S Galv RectFAN 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 SR5-13 1 0.00 0
19 0.0 13.82 ---- Rect. S Galv Rect9 16.0 2,000.0 ---- 0.00 90 0.00050EF 0.0 SR5-14 1 0.00 0
29 0.0 2.89 ---- Rect. S Galv Rect9 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 SR5-13 1 0.00 0
39 0.0 16.53 ---- Rect. S Galv Rect29 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 SR5-21 1 0.00 0
49 0.0 6.55 ---- Rect. S Galv Rect39 16.0 2,000.0 ---- 0.00 90 0.00050EF 0.0 SR5-13 1 0.00 0
59 0.0 15.83 ---- Rect. S Galv Rect39 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 SR5-21 1 0.00 0
69 0.0 12.00 ---- Rect. S Galv Rect59 16.0 2,000.0 ---- 0.00 90 0.00050
EF 0.0 SR5-13 1 0.00 0
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
6/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 6
System 1 "SALA CONTROL" - Trunk Input Data - Return
TrunkUps.
SM
DiaHei
Wid
LengthMax.Vel
Fit 1Fit 2
Junc fit
#Fit#Fit
#Fit
ShapeAdd.Loss
R-Value
ActiveTake Off
Per.Div
Material Ref.Roughness
9 0.0 1.00 ---- Rect. S Galv RectFAN 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 PLENUM 1 0.00 0
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
7/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 7
System 1 "SALA CONTROL" - Runout Input Data - Supply
RunoutUps.
SM
DiaHei
Wid
LengthMax.Vel
Fit 1Fit 2
Fit 3
#Fit#Fit
#Fit
ShapeAdd.Loss
R-Value
ActiveTake Off
NC Level
Material Ref.Roughness
Dif.Loss100 0.0 6.81 ---- Rect. S Galv Rect29 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.100
110 0.0 8.76 ---- Rect. S Galv Rect19 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.060
120 0.0 8.76 ---- Rect. S Galv Rect19 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.060
130 0.0 16.07 ---- Rect. S Galv Rect39 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.070
140 0.0 5.28 ---- Rect. S Galv Rect49 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.100
150 0.0 14.52 CR3-1 1 Rect. S Galv Rect49 16.0 800.0 ---- 0.00 0 0.00050EF 0.0 ---- 0.00 35 0.060
160 0.0 6.81 ---- Rect. S Galv Rect59 16.0 800.0 ---- 0.00 90 0.00050
EF 0.0 ---- 0.00 35 0.100
170 0.0 13.48 ---- Rect. S Galv Rect69 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.060
180 0.0 5.97 ---- Rect. S Galv Rect69 16.0 800.0 ---- 0.00 0 0.00050EF 0.0 ---- 0.00 35 0.060
190 0.0 22.73 CR3-1 1 Rect. S Galv Rect59 16.0 800.0 ---- 0.00 0 0.00050EF 0.0 ---- 0.00 35 0.010
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
8/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 8
System 1 "SALA CONTROL" - Runout Input Data - Return
RunoutUps.
SM
DiaHei
Wid
LengthMax.Vel
Fit 1Fit 2
Fit 3
#Fit#Fit
#Fit
ShapeAdd.Loss
R-Value
ActiveTake Off
NC Level
Material Ref.Roughness
Grille.Loss100 0.0 1.00 ---- Rect. S Galv Rect9 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.039
110 0.0 33.35 ---- Rect. S Galv Rect9 16.0 800.0 ---- 0.00 0 0.00050EF 0.0 ---- 0.00 35 0.039
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
9/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 9
System 1 "SALA CONTROL" - Trunk Output Data - Supply
TrunkUpstrVelCFM
DiaHeiWidLen
SMTOA
Ref
L/100RegGauMat
ShapeFit.1Fit.2
Ups.Junc
QtyQty
Ups.Sh
CoefCoefCoef
Fit------
LossLossLoss
Sect1------
EquipAdd.LF.TotDyna
m
Sect2------
Dynam
FricTotal
Cumul------
Vel.PStat
Total
Press------
VelocStat
Total
9 30.6 EF 0.095 Rect N/A 0.000 0.617 0.000 0.155FAN 16.0 0 0.000 *CR3-1 3 0.867 0.118 0.000 0.036 0.654 0.2001,566/1,333
54.0 22 ---- 0.617 0.654 0.654 0.355
8,000 38.0 Galv Rect 0.617
19 20.7 EF 0.100 Rect Rect 0.000 0.107 0.056 0.0999 16.0 90 -0.050 ---- 0.000 0.014 0.717 0.1361,249/1,095
24.0 24 ---- 0.107 0.120 0.774 0.235
2,920 13.8 Galv Rect SR5-13-BR 1.236 0.107 0.107
29 25.1 EF 0.110 Rect Rect 0.000 0.007 0.017 0.1389 16.0 0 0.010 ---- 0.000 0.003 0.647 0.2071,478/1,345
34.0 22 ---- 0.007 0.010 0.664 0.345
5,080 2.9 Galv Rect SR5-13-MN 0.060 0.007 0.007
39 25.1 EF 0.085 Rect Rect 0.000 0.008 0.050 0.10629 16.0 0 0.025 ---- 0.000 0.014 0.636 0.2181,292/1,175
34.0 22 ---- 0.008 0.022 0.686 0.323
4,440 16.5 Galv Rect *SR5-13-MN 0.085 0.008 0.008
49 10.9 EF 0.110 Rect Rect 0.000 0.167 0.108 0.04739 10.0 90 -0.108 ---- 0.000 0.007 0.752 0.102864/806 10.0 26 ---- 0.167 0.174 0.859 0.149560 6.6 Galv Rect SR5-21-BR 4.051 0.167 0.167
59 20.7 EF 0.095 Rect Rect 0.000 0.012 0.064 0.09139 16.0 0 0.002 ---- 0.000 0.015 0.648 0.2051,202/1,054
24.0 24 ---- 0.012 0.026 0.712 0.297
2,810 15.8 Galv Rect SR5-21-MN 0.147 0.012 0.012
69 16.4 EF 0.095 Rect Rect 0.000 0.093 0.085 0.07059 14.0 90 -0.071 ---- 0.000 0.011 0.731 0.1231,050/990 16.0 24 ---- 0.093 0.105 0.817 0.1921,540 12.0 Galv Rect SR5-21-BR 1.503 0.093 0.093
* Loss coefficient for indicated fitting was extrapolated due to table extents being exceeded.
Explanation of Values in Rightmost Five Columns Above
Column Description"Fit": "Loss" = Static pressure loss through the indicated fitting.
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
10/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 10
System 1 "SALA CONTROL" - Trunk Output Data - Supply (cont'd)
Column Description"Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).
"Add.L" = User entered additional static pressure loss."F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includesloss through central equipment and any loss carried from return system."Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column."Fric" = Static pressure loss due to the inside surface roughness (friction)."Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstreamrunout with highest static pressure minus that of this trunk. For supply, main trunk velocitypressure minus that of this trunk."Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in routestarting with downstream runout with highest static pressure through this trunk. For supply,sum of all upstream trunk losses plus this trunk's loss.
"Total" = Cumulative velocity pressure loss plus cumulative static pressure loss."Press": "Veloc" = Velocity pressure.
"Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit."Total" = Velocity pressure plus static pressure available.
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
11/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 11
System 1 "SALA CONTROL" - Trunk Output Data - Return
TrunkUpstrVelCFM
DiaHeiWidLen
SMTOA
Ref
L/100RegGauMat
ShapeFit.1Fit.2
Ups.Junc
QtyQty
Ups.Sh
CoefCoefCoef
Fit------
LossLossLoss
Sect1------
EquipAdd.LF.TotDyna
m
Sect2------
Dynam
FricTotal
Cumul------
Vel.PStat
Total
Press------
VelocStat
Total
9 33.9 EF 0.055 Rect N/A 0.000 0.000 -0.064 0.099FAN 16.0 0 0.000 ---- 0.000 0.001 0.262 -0.2621,276/1,059
68.0 20 ---- 0.000 0.001 0.199 -0.163
8,000 1.0 Galv Rect 0.000
Explanation of Values in Rightmost Five Columns Above
Column Description
"Fit": "Loss" = Static pressure loss through the indicated fitting."Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).
"Add.L" = User entered additional static pressure loss."F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includesloss through central equipment and any loss carried from return system."Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column."Fric" = Static pressure loss due to the inside surface roughness (friction)."Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstreamrunout with highest static pressure minus that of this trunk. For supply, main trunk velocitypressure minus that of this trunk.
"Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in routestarting with downstream runout with highest static pressure through this trunk. For supply,sum of all upstream trunk losses plus this trunk's loss."Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure."Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit."Total" = Velocity pressure plus static pressure available.
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
12/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 12
System 1 "SALA CONTROL" - Runout Output Data - Supply
Runout
ConnVelCFM
Dia
HeiWidLenOrif
SM
TOA
RefR.NC
L/100
RegGauMatAct.NC
Shape
Fit1Fit2Fit3
Ups.Junc
QtyQtyQtyQty
Ups.S
hCoefCoefCoefCoef
Fit------
LossLossLossLoss
Sect1------
Diff.Add.LF.TotDyna
m
Sect2------
Dynam
FricTotal
Cumul------
Vel.PStat
Total
Press------
VelocStat
Total
100 13.1 EF 0.055 Rect Rect 0.100 0.231 0.126 0.03029 12.0 90 -0.123 ---- 0.000 0.004 0.774 0.080684/640 12.0 24 ---- 0.131 0.235 0.899 0.110640 6.8 Galv Rect ---- 0.231
13.10 35 50 SR5-13-BR 1 5.075 0.131
110 18.5 EF 0.050 Rect Rect 0.060 0.084 0.116 0.03919 16.0 90 -0.024 ---- 0.000 0.004 0.746 0.108782/730 18.0 24 ---- 0.024 0.088 0.862 0.1471,460 8.8 Galv Rect ---- 0.084
18.50 35 50 SR5-14-BR 1 0.720 0.024
120 18.5 EF 0.050 Rect Rect 0.060 0.084 0.116 0.03919 16.0 90 -0.024 ---- 0.000 0.004 0.746 0.108782/730 18.0 24 ---- 0.024 0.088 0.862 0.1471,460 8.8 Galv Rect ---- 0.084
18.50 35 50 SR5-14-BR 1 0.720 0.024
130 16.4 EF 0.050 Rect Rect 0.070 0.185 0.121 0.03439 14.0 90 -0.113 ---- 0.000 0.008 0.757 0.097729/688 16.0 24 ---- 0.115 0.193 0.879 0.1301,070 16.1 Galv Rect ---- 0.185
16.40 35 50 SR5-21-BR 1 3.848 0.115
140 9.7 EF 0.045 Rect Rect 0.100 0.131 0.140 0.01649 8.0 90 -0.100 ---- 0.000 0.002 0.854 0.000497/574 8.0 26 ---- 0.031 0.134 0.993 0.016255 5.3 Galv Rect ---- 0.131
9.70 35 40 SR5-13-BR 1 1.511 0.031
150 9.7 EF 0.065 Rect Rect 0.060 0.070 0.133 0.02249 8.0 0 -0.045 CR3-1 1 0.210 0.006 0.000 0.009 0.805 0.048594/686 8.0 26 ---- 0.010 0.079 0.938 0.071305 14.5 Galv Rect ---- 0.070
9.70 35 40 SR5-13-MN 1 0.111 0.003
160 13.1 EF 0.065 Rect Rect 0.100 0.202 0.121 0.03459 12.0 90 -0.145 ---- 0.000 0.004 0.798 0.056737/690 12.0 24 ---- 0.102 0.207 0.919 0.090690 6.8 Galv Rect ---- 0.202
13.10 35 50 SR5-21-BR 1 3.394 0.102
170 15.3 EF 0.055 Rect Rect 0.060 0.106 0.119 0.03669 14.0 90 -0.072 ---- 0.000 0.008 0.811 0.043756/709 14.0 24 ---- 0.046 0.113 0.930 0.079965 13.5 Galv Rect ---- 0.106
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
13/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 13
System 1 "SALA CONTROL" - Runout Output Data - Supply (cont'd)
Runout
ConnVelCFM
Dia
HeiWidLenOrif
SM
TOA
RefR.NC
L/100
RegGauMatAct.NC
Shape
Fit1Fit2Fit3
Ups.Junc
QtyQtyQtyQty
Ups.S
hCoefCoefCoefCoef
Fit------
LossLossLossLoss
Sect1------
Diff.Add.LF.TotDyna
m
Sect2------
Dynam
FricTotal
Cumul------
Vel.PStat
Total
Press------
VelocStat
Total
15.30 35 35 SR5-13-BR 1 1.443 0.046
180 12.0 EF 0.070 Rect Rect 0.060 0.070 0.121 0.03469 10.0 0 -0.034 ---- 0.000 0.004 0.769 0.084732/690 12.0 24 ---- 0.010 0.074 0.891 0.118575 6.0 Galv Rect ---- 0.070
12.00 35 40 SR5-13-MN 1 0.320 0.010
190 12.0 EF 0.075 Rect Rect 0.010 0.223 0.121 0.03459 10.0 0 -0.166 CR3-1 1 0.729 0.022 0.000 0.017 0.831 0.023738/696 12.0 24 ---- 0.213 0.239 0.952 0.057580 22.7 Galv Rect ---- 0.223
12.00 35 50 SR5-21-MN 1 6.226 0.191
Explanation of Values in Rightmost Five Columns Above
Column Description"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Dif" = User-entered static pressure loss due to the diffuser."Add.L" = User entered additional static pressure loss."F.Tot" = Total of all the fitting static pressure losses."Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column."Fric" = Static pressure loss due to the inside surface roughness (friction)."Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply,velocity pressure of main trunk minus that of this duct."Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum ofall upstream trunk losses plus this runout's loss."Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure."Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit."Total" = Velocity pressure plus static pressure available.
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
14/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 14
System 1 "SALA CONTROL" - Runout Output Data - Return
Runout
ConnVelCFM
Dia
HeiWidLenOrif
SM
TOA
RefR.NC
L/100
RegGauMatAct.NC
Shape
Fit1Fit2Fit3
Ups.Junc
QtyQtyQtyQty
Ups.S
hCoefCoefCoefCoef
Fit------
LossLossLossLoss
Sect1------
Diff.Add.LF.TotDyna
m
Sect2------
Dynam
FricTotal
Cumul------
Vel.PStat
Total
Press------
VelocStat
Total
100 16.4 EF 0.050 Rect Rect 0.039 0.198 0.000 0.0359 14.0 90 -0.134 ---- 0.000 0.001 0.198 0.000764/720 16.0 24 ---- 0.159 0.198 0.198 0.0351,120 1.0 Galv Rect ---- 0.198
16.40 35 50 PLENUM-BR
1 5.045 0.159
110 33.9 EF 0.040 Rect Rect 0.039 0.040 0.000 0.0739 16.0 0 -0.015 ---- 0.000 0.014 0.054 -0.1821,098/911 68.0 20 ---- 0.001 0.054 0.054 -0.1096,880 33.4 Galv Rect ---- 0.040
33.90 35 50 PLENUM-MN
1 0.021 0.001
Explanation of Values in Rightmost Five Columns Above
Column Description"Fit": "Loss" = Static pressure loss through the indicated fitting.
"Sect1": "Dif" = User-entered static pressure loss due to the diffuser."Add.L" = User entered additional static pressure loss."F.Tot" = Total of all the fitting static pressure losses."Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.
"Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column."Fric" = Static pressure loss due to the inside surface roughness (friction)."Total" = Total of the dynamic and friction losses.
"Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply,velocity pressure of main trunk minus that of this duct."Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum ofall upstream trunk losses plus this runout's loss."Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.
"Press": "Veloc" = Velocity pressure."Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit."Total" = Velocity pressure plus static pressure available.
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
15/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 15
System 1 "SALA CONTROL" - Output Summary - SupplyNumber of active trunks: 7Number of active runouts: 10
Total system weight (lb.) minus fittings: 1,673.28Total outlet flow 8,000Total outlet flow after heat gain 8,000Size of largest trunk: 30.6Size of smallest trunk: 10.9Size of largest runout: 18.5Size of smallest runout: 9.7Maximum static pressure loss occurs in route to runout: 140Cumulative static pressure loss at above runout: 0.854Isolate Return From Supply Option: NoReturn SP Loss Added to 1st Trunk of Supply: 0.262
Available static pressure at above runout: 0.000Fan static pressure: 0.854Fan velocity pressure: 0.155Fan total pressure: 1.009
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
16/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 16
System 1 "SALA CONTROL" - Output Summary - ReturnNumber of active trunks: 1Number of active runouts: 2
Total system weight (lb.) minus fittings: 679.26Total outlet flow 8,000Total outlet flow after heat gain 8,000Size of largest trunk: 33.9Size of smallest trunk: 33.9Size of largest runout: 33.9Size of smallest runout: 16.4Maximum SP loss occurs in route from runout: 100Total SP loss of route starting from above runout: 0.262Isolate Return From Supply Option: NoReturn SP Loss Added to 1st Trunk of Supply: 0.262Available static pressure at above runout: 0.000
Fan static pressure: -0.262Fan velocity pressure: 0.099Fan total pressure: -0.163
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
17/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 17
System 1 "SALA CONTROL" - Pressure Changes Graph
-0.3
-0.2
-0.1
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
Pressure,
in.wg
Pressure Changes Through Route with Highest Static Pressure Loss
Static Pressure AvailableTotal Pressure Available
A
B C
D
E FG
H
I
Note: Return side point values are at entrance of duct, while supply side points are at exit. When a returnsystem is present, an additional return side point named [Fan Entrance] is drawn in the graph to show thestatic pressure available at the entrance of the fan. When a supply system is present, and an additionalsupply side point named [Fan Exit] is drawn to show the static pressure available at the exit of the fan.
Point Name Static Pressure Available Total Pressure AvailableA 100 0.000 0.035B 9 -0.262 -0.163C [Fan Entrance] -0.262 -0.163D [Fan Exit] 0.591 0.747E 9 0.200 0.355F 29 0.207 0.345G 39 0.218 0.323H 49 0.102 0.149I 140 0.000 0.016
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.
-
8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control
18/18
Ductsize - HVAC Duct Sizing Elite Software Development, Inc.
GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 18
Duct Connection Tree Diagram - System 1 - SALA CONTROLSystem 1 - SALA CONTROL
Supply
9, EF, Rect, 37.96 ft, 0, SR5-13, 54"x16"
19, EF, Rect, 13.82 ft, 90, SR5-14, 24"x16"
110, EF, Rect, 8.76 ft, 90, 1460 CFM, 18"x16"
120, EF, Rect, 8.76 ft, 90, 1460 CFM, 18"x16"
29, EF, Rect, 2.89 ft, 0, SR5-13, 34"x16"
100, EF, Rect, 6.81 ft, 90, 640 CFM, 12"x12"
39, EF, Rect, 16.53 ft, 0, SR5-21, 34"x16"
130, EF, Rect, 16.07 ft, 90, 1070 CFM, 16"x14"
49, EF, Rect, 6.55 ft, 90, SR5-13, 10"x10"
140, EF, Rect, 5.28 ft, 90, 255 CFM, 8"x8"
150, EF, Rect, 14.52 ft, 0, 305 CFM, 8"x8"59, EF, Rect, 15.83 ft, 0, SR5-21, 24"x16"
160, EF, Rect, 6.81 ft, 90, 690 CFM, 12"x12"
190, EF, Rect, 22.73 ft, 0, 580 CFM, 12"x10"
69, EF, Rect, 12 ft, 90, SR5-13, 16"x14"
170, EF, Rect, 13.48 ft, 90, 965 CFM, 14"x14"
180, EF, Rect, 5.97 ft, 0, 575 CFM, 12"x10"
Return
9, EF, Rect, 1 ft, 0, PLENUM, 68"x16"
100, EF, Rect, 1 ft, 90, 1120 CFM, 16"x14"
110, EF, Rect, 33.35 ft, 0, 6880 CFM, 68"x16"
D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.