    GENER. ELCTRICA MVIL CACIQUE CHAIMAHVAC Duct Sizing

    for

    PDVSA

    Prepared By:

    VENINCO

    Domingo, 21 de Octubre de 2012

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    2/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 2

    General Project Data Input

    General Project InformationProject file name: D:\ELITE\SALA CONTROL GENER. ELCT.

    MVIL CACIQUE CHAIMA.dswProject title: GENER. ELCTRICA MVIL CACIQUE CHAIMADesigned by: CONRAD GOLDSTEINProject date: Lunes, 03 de Septiembre de 2012Project comment: SALA DE CONTROLClient name: PDVSACompany name: VENINCO

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    3/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 3

    System 1 "SALA CONTROL" - Input Data - Supply

    Project & Default Data Trunks RunoutsMaximum desired velocity (FPM): 2,000 800

    Material Reference: Galv Rect Galv RectHeight constraint (in): 16 16Width constraint (in): 0 0Diameter constraint (in): 0 0R-Value of insulation (Sq.ft.F/Btuh): 0.00 0.00Duct shape: Rect. Rect.Sizing method: EF EFNC criteria: N/A 35

    Duct System DataMaximum system velocity (FPM): 2,000.0Minimum system velocity (FPM): 650.0Minimum trunk diameter (in): 0.0

    Orifice opening interval (in): 0.000Temperature of air leaving coil (F): 55Design room temperature (F): 75Temperature of duct installation space (F): 0Altitude (ft): 262Density (lb/cu.ft): 0.076Friction loss per 100 ft. (in.wg): 0.100Est. st. press. loss of central equip. (in.wg): 0.000Maximum % supply air increase: 0Allow increasing downstream diameters: NoShow diversified trunk flows: NoDuct diameter interval (in): 0.0Whole number dimensions: S

    Fan DataFan description: CENT-FORWARD

    CURVEDFan static pressure (in.wg): 0.000Fan CFM: 0Fan efficiency: 0Fan RPM: 0Number of blades: 0Fan blast width (in): 0Fan blast height (in): 0Length to first fitting (ft): 0.0

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    4/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 4

    System 1 "SALA CONTROL" - Input Data - Return

    Project & Default Data Trunks RunoutsMaximum desired velocity (FPM): 2,000 800

    Material Reference: Galv Rect Galv RectHeight constraint (in): 16 16Width constraint (in): 0 0Diameter constraint (in): 0 0R-Value of insulation (Sq.ft.F/Btuh): 0.00 0.00Duct shape: Rect. Rect.Sizing method: EF EFNC criteria: N/A 35

    Duct System DataMaximum system velocity (FPM): 2,000.0Minimum system velocity (FPM): 650.0Minimum trunk diameter (in): 0.0

    Orifice opening interval (in): 0.000Temperature of air leaving coil (F): 75Design room temperature (F): 75Temperature of duct installation space (F): 0Altitude (ft): 262Density (lb/cu.ft): 0.073Friction loss per 100 ft. (in.wg): 0.050Est. st. press. loss of central equip. (in.wg): 0.000Maximum % supply air increase: 0Allow increasing downstream diameters: NoShow diversified trunk flows: NoDuct diameter interval (in): 0.0Whole number dimensions: S

    Fan DataFan description: CENT-FORWARD

    CURVEDFan static pressure (in.wg): 0.000Fan CFM: 0Fan efficiency: 0Fan RPM: 0Number of blades: 0Fan blast width (in): 0Fan blast height (in): 0Length to first fitting (ft): 0.0

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    5/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 5

    System 1 "SALA CONTROL" - Trunk Input Data - Supply

    TrunkUps.

    SM

    DiaHei

    Wid

    LengthMax.Vel

    Fit 1Fit 2

    Junc fit

    #Fit#Fit

    #Fit

    ShapeAdd.Loss

    R-Value

    ActiveTake Off

    Per.Div

    Material Ref.Roughness

    9 0.0 37.96 CR3-1 3 Rect. S Galv RectFAN 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 SR5-13 1 0.00 0

    19 0.0 13.82 ---- Rect. S Galv Rect9 16.0 2,000.0 ---- 0.00 90 0.00050EF 0.0 SR5-14 1 0.00 0

    29 0.0 2.89 ---- Rect. S Galv Rect9 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 SR5-13 1 0.00 0

    39 0.0 16.53 ---- Rect. S Galv Rect29 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 SR5-21 1 0.00 0

    49 0.0 6.55 ---- Rect. S Galv Rect39 16.0 2,000.0 ---- 0.00 90 0.00050EF 0.0 SR5-13 1 0.00 0

    59 0.0 15.83 ---- Rect. S Galv Rect39 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 SR5-21 1 0.00 0

    69 0.0 12.00 ---- Rect. S Galv Rect59 16.0 2,000.0 ---- 0.00 90 0.00050

    EF 0.0 SR5-13 1 0.00 0

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    6/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 6

    System 1 "SALA CONTROL" - Trunk Input Data - Return

    TrunkUps.

    SM

    DiaHei

    Wid

    LengthMax.Vel

    Fit 1Fit 2

    Junc fit

    #Fit#Fit

    #Fit

    ShapeAdd.Loss

    R-Value

    ActiveTake Off

    Per.Div

    Material Ref.Roughness

    9 0.0 1.00 ---- Rect. S Galv RectFAN 16.0 2,000.0 ---- 0.00 0 0.00050EF 0.0 PLENUM 1 0.00 0

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    7/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 7

    System 1 "SALA CONTROL" - Runout Input Data - Supply

    RunoutUps.

    SM

    DiaHei

    Wid

    LengthMax.Vel

    Fit 1Fit 2

    Fit 3

    #Fit#Fit

    #Fit

    ShapeAdd.Loss

    R-Value

    ActiveTake Off

    NC Level

    Material Ref.Roughness

    Dif.Loss100 0.0 6.81 ---- Rect. S Galv Rect29 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.100

    110 0.0 8.76 ---- Rect. S Galv Rect19 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.060

    120 0.0 8.76 ---- Rect. S Galv Rect19 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.060

    130 0.0 16.07 ---- Rect. S Galv Rect39 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.070

    140 0.0 5.28 ---- Rect. S Galv Rect49 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.100

    150 0.0 14.52 CR3-1 1 Rect. S Galv Rect49 16.0 800.0 ---- 0.00 0 0.00050EF 0.0 ---- 0.00 35 0.060

    160 0.0 6.81 ---- Rect. S Galv Rect59 16.0 800.0 ---- 0.00 90 0.00050

    EF 0.0 ---- 0.00 35 0.100

    170 0.0 13.48 ---- Rect. S Galv Rect69 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.060

    180 0.0 5.97 ---- Rect. S Galv Rect69 16.0 800.0 ---- 0.00 0 0.00050EF 0.0 ---- 0.00 35 0.060

    190 0.0 22.73 CR3-1 1 Rect. S Galv Rect59 16.0 800.0 ---- 0.00 0 0.00050EF 0.0 ---- 0.00 35 0.010

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    8/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 8

    System 1 "SALA CONTROL" - Runout Input Data - Return

    RunoutUps.

    SM

    DiaHei

    Wid

    LengthMax.Vel

    Fit 1Fit 2

    Fit 3

    #Fit#Fit

    #Fit

    ShapeAdd.Loss

    R-Value

    ActiveTake Off

    NC Level

    Material Ref.Roughness

    Grille.Loss100 0.0 1.00 ---- Rect. S Galv Rect9 16.0 800.0 ---- 0.00 90 0.00050EF 0.0 ---- 0.00 35 0.039

    110 0.0 33.35 ---- Rect. S Galv Rect9 16.0 800.0 ---- 0.00 0 0.00050EF 0.0 ---- 0.00 35 0.039

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    9/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 9

    System 1 "SALA CONTROL" - Trunk Output Data - Supply

    TrunkUpstrVelCFM

    DiaHeiWidLen

    SMTOA

    Ref

    L/100RegGauMat

    ShapeFit.1Fit.2

    Ups.Junc

    QtyQty

    Ups.Sh

    CoefCoefCoef

    Fit------

    LossLossLoss

    Sect1------

    EquipAdd.LF.TotDyna

    m

    Sect2------

    Dynam

    FricTotal

    Cumul------

    Vel.PStat

    Total

    Press------

    VelocStat

    Total

    9 30.6 EF 0.095 Rect N/A 0.000 0.617 0.000 0.155FAN 16.0 0 0.000 *CR3-1 3 0.867 0.118 0.000 0.036 0.654 0.2001,566/1,333

    54.0 22 ---- 0.617 0.654 0.654 0.355

    8,000 38.0 Galv Rect 0.617

    19 20.7 EF 0.100 Rect Rect 0.000 0.107 0.056 0.0999 16.0 90 -0.050 ---- 0.000 0.014 0.717 0.1361,249/1,095

    24.0 24 ---- 0.107 0.120 0.774 0.235

    2,920 13.8 Galv Rect SR5-13-BR 1.236 0.107 0.107

    29 25.1 EF 0.110 Rect Rect 0.000 0.007 0.017 0.1389 16.0 0 0.010 ---- 0.000 0.003 0.647 0.2071,478/1,345

    34.0 22 ---- 0.007 0.010 0.664 0.345

    5,080 2.9 Galv Rect SR5-13-MN 0.060 0.007 0.007

    39 25.1 EF 0.085 Rect Rect 0.000 0.008 0.050 0.10629 16.0 0 0.025 ---- 0.000 0.014 0.636 0.2181,292/1,175

    34.0 22 ---- 0.008 0.022 0.686 0.323

    4,440 16.5 Galv Rect *SR5-13-MN 0.085 0.008 0.008

    49 10.9 EF 0.110 Rect Rect 0.000 0.167 0.108 0.04739 10.0 90 -0.108 ---- 0.000 0.007 0.752 0.102864/806 10.0 26 ---- 0.167 0.174 0.859 0.149560 6.6 Galv Rect SR5-21-BR 4.051 0.167 0.167

    59 20.7 EF 0.095 Rect Rect 0.000 0.012 0.064 0.09139 16.0 0 0.002 ---- 0.000 0.015 0.648 0.2051,202/1,054

    24.0 24 ---- 0.012 0.026 0.712 0.297

    2,810 15.8 Galv Rect SR5-21-MN 0.147 0.012 0.012

    69 16.4 EF 0.095 Rect Rect 0.000 0.093 0.085 0.07059 14.0 90 -0.071 ---- 0.000 0.011 0.731 0.1231,050/990 16.0 24 ---- 0.093 0.105 0.817 0.1921,540 12.0 Galv Rect SR5-21-BR 1.503 0.093 0.093

    * Loss coefficient for indicated fitting was extrapolated due to table extents being exceeded.

    Explanation of Values in Rightmost Five Columns Above

    Column Description"Fit": "Loss" = Static pressure loss through the indicated fitting.

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    10/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 10

    System 1 "SALA CONTROL" - Trunk Output Data - Supply (cont'd)

    Column Description"Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).

    "Add.L" = User entered additional static pressure loss."F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includesloss through central equipment and any loss carried from return system."Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.

    "Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column."Fric" = Static pressure loss due to the inside surface roughness (friction)."Total" = Total of the dynamic and friction losses.

    "Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstreamrunout with highest static pressure minus that of this trunk. For supply, main trunk velocitypressure minus that of this trunk."Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in routestarting with downstream runout with highest static pressure through this trunk. For supply,sum of all upstream trunk losses plus this trunk's loss.

    "Total" = Cumulative velocity pressure loss plus cumulative static pressure loss."Press": "Veloc" = Velocity pressure.

    "Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit."Total" = Velocity pressure plus static pressure available.

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    11/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 11

    System 1 "SALA CONTROL" - Trunk Output Data - Return

    TrunkUpstrVelCFM

    DiaHeiWidLen

    SMTOA

    Ref

    L/100RegGauMat

    ShapeFit.1Fit.2

    Ups.Junc

    QtyQty

    Ups.Sh

    CoefCoefCoef

    Fit------

    LossLossLoss

    Sect1------

    EquipAdd.LF.TotDyna

    m

    Sect2------

    Dynam

    FricTotal

    Cumul------

    Vel.PStat

    Total

    Press------

    VelocStat

    Total

    9 33.9 EF 0.055 Rect N/A 0.000 0.000 -0.064 0.099FAN 16.0 0 0.000 ---- 0.000 0.001 0.262 -0.2621,276/1,059

    68.0 20 ---- 0.000 0.001 0.199 -0.163

    8,000 1.0 Galv Rect 0.000

    Explanation of Values in Rightmost Five Columns Above

    Column Description

    "Fit": "Loss" = Static pressure loss through the indicated fitting."Sect1": "Equip" = User-entered loss through central equipment (supply main trunk only).

    "Add.L" = User entered additional static pressure loss."F.Tot" = Total of all the fitting static pressure losses. For supply main trunk, also includesloss through central equipment and any loss carried from return system."Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.

    "Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column."Fric" = Static pressure loss due to the inside surface roughness (friction)."Total" = Total of the dynamic and friction losses.

    "Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, velocity pressure of downstreamrunout with highest static pressure minus that of this trunk. For supply, main trunk velocitypressure minus that of this trunk.

    "Stat" = Cumulative loss of static pressure. For return, sum of the loss of all ducts in routestarting with downstream runout with highest static pressure through this trunk. For supply,sum of all upstream trunk losses plus this trunk's loss."Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.

    "Press": "Veloc" = Velocity pressure."Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit."Total" = Velocity pressure plus static pressure available.

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    12/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 12

    System 1 "SALA CONTROL" - Runout Output Data - Supply

    Runout

    ConnVelCFM

    Dia

    HeiWidLenOrif

    SM

    TOA

    RefR.NC

    L/100

    RegGauMatAct.NC

    Shape

    Fit1Fit2Fit3

    Ups.Junc

    QtyQtyQtyQty

    Ups.S

    hCoefCoefCoefCoef

    Fit------

    LossLossLossLoss

    Sect1------

    Diff.Add.LF.TotDyna

    m

    Sect2------

    Dynam

    FricTotal

    Cumul------

    Vel.PStat

    Total

    Press------

    VelocStat

    Total

    100 13.1 EF 0.055 Rect Rect 0.100 0.231 0.126 0.03029 12.0 90 -0.123 ---- 0.000 0.004 0.774 0.080684/640 12.0 24 ---- 0.131 0.235 0.899 0.110640 6.8 Galv Rect ---- 0.231

    13.10 35 50 SR5-13-BR 1 5.075 0.131

    110 18.5 EF 0.050 Rect Rect 0.060 0.084 0.116 0.03919 16.0 90 -0.024 ---- 0.000 0.004 0.746 0.108782/730 18.0 24 ---- 0.024 0.088 0.862 0.1471,460 8.8 Galv Rect ---- 0.084

    18.50 35 50 SR5-14-BR 1 0.720 0.024

    120 18.5 EF 0.050 Rect Rect 0.060 0.084 0.116 0.03919 16.0 90 -0.024 ---- 0.000 0.004 0.746 0.108782/730 18.0 24 ---- 0.024 0.088 0.862 0.1471,460 8.8 Galv Rect ---- 0.084

    18.50 35 50 SR5-14-BR 1 0.720 0.024

    130 16.4 EF 0.050 Rect Rect 0.070 0.185 0.121 0.03439 14.0 90 -0.113 ---- 0.000 0.008 0.757 0.097729/688 16.0 24 ---- 0.115 0.193 0.879 0.1301,070 16.1 Galv Rect ---- 0.185

    16.40 35 50 SR5-21-BR 1 3.848 0.115

    140 9.7 EF 0.045 Rect Rect 0.100 0.131 0.140 0.01649 8.0 90 -0.100 ---- 0.000 0.002 0.854 0.000497/574 8.0 26 ---- 0.031 0.134 0.993 0.016255 5.3 Galv Rect ---- 0.131

    9.70 35 40 SR5-13-BR 1 1.511 0.031

    150 9.7 EF 0.065 Rect Rect 0.060 0.070 0.133 0.02249 8.0 0 -0.045 CR3-1 1 0.210 0.006 0.000 0.009 0.805 0.048594/686 8.0 26 ---- 0.010 0.079 0.938 0.071305 14.5 Galv Rect ---- 0.070

    9.70 35 40 SR5-13-MN 1 0.111 0.003

    160 13.1 EF 0.065 Rect Rect 0.100 0.202 0.121 0.03459 12.0 90 -0.145 ---- 0.000 0.004 0.798 0.056737/690 12.0 24 ---- 0.102 0.207 0.919 0.090690 6.8 Galv Rect ---- 0.202

    13.10 35 50 SR5-21-BR 1 3.394 0.102

    170 15.3 EF 0.055 Rect Rect 0.060 0.106 0.119 0.03669 14.0 90 -0.072 ---- 0.000 0.008 0.811 0.043756/709 14.0 24 ---- 0.046 0.113 0.930 0.079965 13.5 Galv Rect ---- 0.106

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    13/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 13

    System 1 "SALA CONTROL" - Runout Output Data - Supply (cont'd)

    Runout

    ConnVelCFM

    Dia

    HeiWidLenOrif

    SM

    TOA

    RefR.NC

    L/100

    RegGauMatAct.NC

    Shape

    Fit1Fit2Fit3

    Ups.Junc

    QtyQtyQtyQty

    Ups.S

    hCoefCoefCoefCoef

    Fit------

    LossLossLossLoss

    Sect1------

    Diff.Add.LF.TotDyna

    m

    Sect2------

    Dynam

    FricTotal

    Cumul------

    Vel.PStat

    Total

    Press------

    VelocStat

    Total

    15.30 35 35 SR5-13-BR 1 1.443 0.046

    180 12.0 EF 0.070 Rect Rect 0.060 0.070 0.121 0.03469 10.0 0 -0.034 ---- 0.000 0.004 0.769 0.084732/690 12.0 24 ---- 0.010 0.074 0.891 0.118575 6.0 Galv Rect ---- 0.070

    12.00 35 40 SR5-13-MN 1 0.320 0.010

    190 12.0 EF 0.075 Rect Rect 0.010 0.223 0.121 0.03459 10.0 0 -0.166 CR3-1 1 0.729 0.022 0.000 0.017 0.831 0.023738/696 12.0 24 ---- 0.213 0.239 0.952 0.057580 22.7 Galv Rect ---- 0.223

    12.00 35 50 SR5-21-MN 1 6.226 0.191

    Explanation of Values in Rightmost Five Columns Above

    Column Description"Fit": "Loss" = Static pressure loss through the indicated fitting.

    "Sect1": "Dif" = User-entered static pressure loss due to the diffuser."Add.L" = User entered additional static pressure loss."F.Tot" = Total of all the fitting static pressure losses."Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.

    "Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column."Fric" = Static pressure loss due to the inside surface roughness (friction)."Total" = Total of the dynamic and friction losses.

    "Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply,velocity pressure of main trunk minus that of this duct."Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum ofall upstream trunk losses plus this runout's loss."Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.

    "Press": "Veloc" = Velocity pressure."Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit."Total" = Velocity pressure plus static pressure available.

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    14/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 14

    System 1 "SALA CONTROL" - Runout Output Data - Return

    Runout

    ConnVelCFM

    Dia

    HeiWidLenOrif

    SM

    TOA

    RefR.NC

    L/100

    RegGauMatAct.NC

    Shape

    Fit1Fit2Fit3

    Ups.Junc

    QtyQtyQtyQty

    Ups.S

    hCoefCoefCoefCoef

    Fit------

    LossLossLossLoss

    Sect1------

    Diff.Add.LF.TotDyna

    m

    Sect2------

    Dynam

    FricTotal

    Cumul------

    Vel.PStat

    Total

    Press------

    VelocStat

    Total

    100 16.4 EF 0.050 Rect Rect 0.039 0.198 0.000 0.0359 14.0 90 -0.134 ---- 0.000 0.001 0.198 0.000764/720 16.0 24 ---- 0.159 0.198 0.198 0.0351,120 1.0 Galv Rect ---- 0.198

    16.40 35 50 PLENUM-BR

    1 5.045 0.159

    110 33.9 EF 0.040 Rect Rect 0.039 0.040 0.000 0.0739 16.0 0 -0.015 ---- 0.000 0.014 0.054 -0.1821,098/911 68.0 20 ---- 0.001 0.054 0.054 -0.1096,880 33.4 Galv Rect ---- 0.040

    33.90 35 50 PLENUM-MN

    1 0.021 0.001

    Explanation of Values in Rightmost Five Columns Above

    Column Description"Fit": "Loss" = Static pressure loss through the indicated fitting.

    "Sect1": "Dif" = User-entered static pressure loss due to the diffuser."Add.L" = User entered additional static pressure loss."F.Tot" = Total of all the fitting static pressure losses."Dynam" = Total of all the dynamic losses, which includes everything but the frictional loss.

    "Sect2": "Dynam" = Total of the dynamic losses, carried from bottom of previous column."Fric" = Static pressure loss due to the inside surface roughness (friction)."Total" = Total of the dynamic and friction losses.

    "Cumul": "Vel.P" = Cumulative loss in velocity pressure. For return, zero for each runout. For supply,velocity pressure of main trunk minus that of this duct."Stat" = Cumulative loss of static pressure. For return, this runout's loss. For supply, sum ofall upstream trunk losses plus this runout's loss."Total" = Cumulative velocity pressure loss plus cumulative static pressure loss.

    "Press": "Veloc" = Velocity pressure."Stat" = Static pressure available. For return, at entrance of duct. For supply, at exit."Total" = Velocity pressure plus static pressure available.

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    15/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 15

    System 1 "SALA CONTROL" - Output Summary - SupplyNumber of active trunks: 7Number of active runouts: 10

    Total system weight (lb.) minus fittings: 1,673.28Total outlet flow 8,000Total outlet flow after heat gain 8,000Size of largest trunk: 30.6Size of smallest trunk: 10.9Size of largest runout: 18.5Size of smallest runout: 9.7Maximum static pressure loss occurs in route to runout: 140Cumulative static pressure loss at above runout: 0.854Isolate Return From Supply Option: NoReturn SP Loss Added to 1st Trunk of Supply: 0.262

    Available static pressure at above runout: 0.000Fan static pressure: 0.854Fan velocity pressure: 0.155Fan total pressure: 1.009

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    16/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 16

    System 1 "SALA CONTROL" - Output Summary - ReturnNumber of active trunks: 1Number of active runouts: 2

    Total system weight (lb.) minus fittings: 679.26Total outlet flow 8,000Total outlet flow after heat gain 8,000Size of largest trunk: 33.9Size of smallest trunk: 33.9Size of largest runout: 33.9Size of smallest runout: 16.4Maximum SP loss occurs in route from runout: 100Total SP loss of route starting from above runout: 0.262Isolate Return From Supply Option: NoReturn SP Loss Added to 1st Trunk of Supply: 0.262Available static pressure at above runout: 0.000

    Fan static pressure: -0.262Fan velocity pressure: 0.099Fan total pressure: -0.163

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    17/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 17

    System 1 "SALA CONTROL" - Pressure Changes Graph

    -0.3

    -0.2

    -0.1

    0.0

    0.1

    0.2

    0.3

    0.4

    0.5

    0.6

    0.7

    0.8

    Pressure,

    in.wg

    Pressure Changes Through Route with Highest Static Pressure Loss

    Static Pressure AvailableTotal Pressure Available

    A

    B C

    D

    E FG

    H

    I

    Note: Return side point values are at entrance of duct, while supply side points are at exit. When a returnsystem is present, an additional return side point named [Fan Entrance] is drawn in the graph to show thestatic pressure available at the entrance of the fan. When a supply system is present, and an additionalsupply side point named [Fan Exit] is drawn to show the static pressure available at the exit of the fan.

    Point Name Static Pressure Available Total Pressure AvailableA 100 0.000 0.035B 9 -0.262 -0.163C [Fan Entrance] -0.262 -0.163D [Fan Exit] 0.591 0.747E 9 0.200 0.355F 29 0.207 0.345G 39 0.218 0.323H 49 0.102 0.149I 140 0.000 0.016

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.

  • 8/13/2019 Anexo 12 Corrida de Calculos Ductos Sala de Control

    18/18

    Ductsize - HVAC Duct Sizing Elite Software Development, Inc.

    GOLDSPARR S.C. GENER. ELCTRICA MVIL CACIQUE CHAIMAPage 18

    Duct Connection Tree Diagram - System 1 - SALA CONTROLSystem 1 - SALA CONTROL

    Supply

    9, EF, Rect, 37.96 ft, 0, SR5-13, 54"x16"

    19, EF, Rect, 13.82 ft, 90, SR5-14, 24"x16"

    110, EF, Rect, 8.76 ft, 90, 1460 CFM, 18"x16"

    120, EF, Rect, 8.76 ft, 90, 1460 CFM, 18"x16"

    29, EF, Rect, 2.89 ft, 0, SR5-13, 34"x16"

    100, EF, Rect, 6.81 ft, 90, 640 CFM, 12"x12"

    39, EF, Rect, 16.53 ft, 0, SR5-21, 34"x16"

    130, EF, Rect, 16.07 ft, 90, 1070 CFM, 16"x14"

    49, EF, Rect, 6.55 ft, 90, SR5-13, 10"x10"

    140, EF, Rect, 5.28 ft, 90, 255 CFM, 8"x8"

    150, EF, Rect, 14.52 ft, 0, 305 CFM, 8"x8"59, EF, Rect, 15.83 ft, 0, SR5-21, 24"x16"

    160, EF, Rect, 6.81 ft, 90, 690 CFM, 12"x12"

    190, EF, Rect, 22.73 ft, 0, 580 CFM, 12"x10"

    69, EF, Rect, 12 ft, 90, SR5-13, 16"x14"

    170, EF, Rect, 13.48 ft, 90, 965 CFM, 14"x14"

    180, EF, Rect, 5.97 ft, 0, 575 CFM, 12"x10"

    Return

    9, EF, Rect, 1 ft, 0, PLENUM, 68"x16"

    100, EF, Rect, 1 ft, 90, 1120 CFM, 16"x14"

    110, EF, Rect, 33.35 ft, 0, 6880 CFM, 68"x16"

    D:\ ...\SALA CONTROL ... E CHAIMA.dsw Domingo, 21 de Octubre de 2012, 4:52 p.m.